inStallation checKliSt

electrical SyStem

Electrical connections tight?

YES

NO

Line voltage polarity correct?

YES

NO

Rated Voltage: ___________________________________ VOLTS

L1-L2 Volts: _____________________________________ VOLTS

L1-L3 Volts: _____________________________________ VOLTS

L2-L3 Volts: _____________________________________ VOLTS

Avg. Volts: ______________________________________ VOLTS

Max. deviation of voltage
from avg. volts: ___________________________________ VOLTS

% Volt imbalance: ________________________________ VOLTS

Blower Motor HP: ________ Sheave Setting ___________# Turns

Has the thermostat been calibrated?

YES

NO

Is the thermostat level?

YES

NO

Is the heat anticipator setting 

correct? (If Applicable)

YES

NO

inStallation addreSS:

CITY ________________________ STATE ________________

UNIT MODEL # ________________________________________

UNIT SERIAL # _______________________________________

Unit Installed Minimum clearances 

per 

Figure 1, (page 3)

?

YES

NO

inStaller name:

CITY _______________________

STATE ________________

reFrigeration SyStem:

Was unit given 24 hr warm up period 

for crankcase heaters?

YES

NO

Stage-1 Liquid Pressure (high side) ________________________

Stage-1 Suction Pressure (low side) ________________________

Has the owner’s information been 

reviewed with the customer?

YES

NO

Has the Literature Package been left 

with the unit?

YES

NO

709713a 

(Replaces 7097130)

replacement partS

Replacement parts are available through your distributor 

distributors. Please have the complete model and serial 

number of the unit when ordering replacement parts.

electrical:

•  Capacitors

•  Temperature Limit Switches

•  Compressors

•  Thermostats

•  Contactors

•  Time Delay Relays

•  Pressure Switches

•  Transformers

•  Relays

motors:

•  Blower Motor
•  Fan Motor

components:

•  Blower Assembly

•  Fan Grille

•  Cabinet Panels

•  Filter/Driers

•  Expansion Valves

Specifications & illustrations subject to change without notice or incurring obligations (11/15).
O’Fallon, MO, © Nortek Global HVAC LLC 2015. All Rights Reserved.

Содержание DS4BF

Страница 1: ...ckage for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE Installation Instructions important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 Genera...

Страница 2: ...tions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operation...

Страница 3: ...g the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit The outdoor unit should be installed no closer than 18 inches from the outside...

Страница 4: ...of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre E...

Страница 5: ...is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 15 Compressor Protection TheCoreS...

Страница 6: ...e fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to HEAT and the...

Страница 7: ...ded Deviationsfromratedairflowsor non listedcombinationsmayrequiremodificationtothe expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charg...

Страница 8: ...abel Charging charts are valid for a variety of indoor return air conditions and are most influenced by the outdoor ambienttemperature outdoorfanoperationandtheunit operatingvoltage Beforeusingthesech...

Страница 9: ...onductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circu...

Страница 10: ...R C S S C R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Cr...

Страница 11: ...le Phase 60 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR...

Страница 12: ...tection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avan...

Страница 13: ...ACTS L1 T1 COMPRESSOR CSC C Y2 Y LPS HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz...

Страница 14: ...class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducte...

Страница 15: ...functioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant Charge Discharge pres...

Страница 16: ...seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blower motor capacito...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...______________________ Unit Installed Minimum clearances per Figure 1 page 3 YES NO INSTALLER NAME CITY________________________ STATE_________________ REFRIGERATION SYSTEM Was unit given 24 hr warm up...

Отзывы: