13
AirCare
®
ACC1 Console Technical Manual
If fault contacts or pressure switches are used, these will be monitored on all control modules.
The control modules will continue to function normally if a connection to the network or console is lost.
If power is turned off & on to any module or console in the network, its functionality and settings will be immediately
restored to the same state before power loss.
POWER-ON SEQUENCE
At power-on, the console displays (for 1 second)
- firmware version major
- firmware version minor
- model number
Then the console scans the network to identify all modules connected, also ACM1007 and ACM1009
modules. If no controller modules are detected, the console beeps and repeats the scan sequence until
at least one module is found.
When finished, the console will display (for 1 second):
Top display
The maximum number of control modules possible
Middle display
‘rS’ if an ACM1007 is found at address 251 (standby switch input), ‘ES’ if an ACM1007 is found at
address 252 (emergency stop input), ‘rL’ if an ACM1009 is found at address 253 (error output relay
driver)
Bottom display
The total number of control modules found
After 1 second, the console goes into monitor mode and is ready for operation.
MONITOR MODE
The console will go to monitor mode after the select and adjust knobs are not moved for 30 seconds.
In monitor mode, the console continuously polls all modules on the network. The following information is displayed: