OPTIONAL ACM1015 NETWORKING ADVANCED MANUAL
REGISTERS:
The fan speed feedback is the best way of monitoring fan status. It is off an actual tachometer output from the motor that
is from the inherent sensor built into the motor. Actual feedback from the tachometer sensor in the motor is located in
Register 6. Register 6 is the best way of monitoring fan status.
Register 1 is used for stopping (0) and starting (1) the unit while power is on.
Register 14 is used to determine default run status, stop (0) or start
(1) upon power up. To change the speed of the motor while the system is powered the operator should use Register 2.
Once the room is balanced, the individual FFU speed settings (0- 100%) should be entered into Register 10. This is the
default speed setting, which the card sends to the motor upon power up.
ACM1015 MODBUS
®
Equipped Interface for EBM Brushless DC Motors
www.aircareautomation.com