6

8)  Remove the corresponding drain line 

knockout from the coil access door to allow 
access to the horizontal drain.

9)  Replace the door.

NOTE: 

 Install drainpan extension (supplied) on 

the following models:
C5BH-*60 

C4BH-X36

C5BH-*49 

C4BH-X48

 

 

C4BH-X60

Note: All condensate pans have primary and 
secondary drain connections to meet FHA 
requirements. If the application is located in 
or above a living space where damage may 
result from condensate overflow, a separate 
3/4 inch drain must be provided from the 
secondary drain connection and a secondary 
drain pan must be installed under the entire 
unit. Run secondary drain lines to a place 
where they are noticeable if used.

4.  VERIFY PRESSURIZATION 

 

WARNING:

This coil is pressurized with Nitrogen.  
Avoid direct face exposure or contact 
with valve when gas is escaping. 
Always ensure adequate ventilation 
is present during the depressurization 
process.  Any uncertainties should be 

addressed before proceeding.

VERIFY PRESSURIZATION:

Test by depressing Schrader valve and listen 
for escaping gas

-  If no pressure is found, test coil for leak

- If no leak is found, install coil
- If leak is found, clearly mark leak 

 

location and return coil to your distributor 
for processing

5. REFRIGERANT LINE  

 

    CONNECTIONS

 

WARNING:

This coil is pressurized with Nitrogen.  
Avoid direct face exposure or contact 
with valve when gas is escaping. 
Always ensure adequate ventilation 
is present during the depressurization 
process.  Any uncertainties should be 

addressed before proceeding.

NOTE:

 For coils with factory installed TXV valve 

proceed to step #8. 

NOTE:

 Before proceeding with the connection of 

the refrigerant lines, confirm that the orifice size 

meets the requirements outlined in the outdoor 

unit installation manual. Factory installed orifice 
sizes are listed in the Specifications section. If 
the  restrictor  orifice  must  be  replaced,  follow 
the steps below:

1.  Remove the valve cap from the end of the 

liquid line.  Relieve all pressure from the 
coil by depressing the valve.  Remove the 

valve core.  Properly dispose of all removed 

parts. 

2.  Loosen the orifice/distributor body halves by 

applying two wrenches and squeezing them 
together, as shown in Figure 3 , to turn the 
assembly nut counter-clockwise.

3.  Continue  to  unscrew  the  assembly  nut 

to separate it from the distributor body 
portion.

4.  Insert a light-gauge wire hook between the 

distributor body and the orifice to lift the 

orifice out of the body. (See Figure 4) Remove 

the orifice being careful not to scratch either 
part.

5.  Check the actual size of the new orifice (the 

size is stamped on the side of the orifice).  
Do not use pin gauges to measure the orifice 

diameter.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Содержание C5B

Страница 1: ...tionsand orfurnace air handler markings before proceeding with installation of the coil These instructions are primarily intended to assist qualified individuals experienced in the proper installation...

Страница 2: ...izontal Furnace Horizontal Ready Coils for Horizontal Left Installation Horizontal Ready Coils for Horizontal Right Installation 4 Verify Pressurization 6 5 Refrigerant Line Connections 6 6 Completing...

Страница 3: ...tdoor unit NOTE Some coils employ a thermostatic expansion valve TXV as the metering device See page 4 H 20 3 4 B 16 5 8 W A 3 4 133 8 155 8 19 3 4 Figure 1 3 Wherepreciseformingoftherefrigerantlines...

Страница 4: ...63 913963 913963 913964 913964 913964 Extra Orifice in N A 0 053 for 1 5 ton condenser N A N A 0 053 for 1 5 ton condenser N A N A N A N A N A N A N A N A Coil Model 1 C5BA H T X24C A C5BA H T25C A C5...

Страница 5: ...the threaded holes of the horizontal drain pan If webbing is not removed the drain will not function properly and ceiling damage may occur 3 Insert a plug from the horizontal drain pan into the open a...

Страница 6: ...id direct face exposure or contact with valve when gas is escaping Always ensure adequate ventilation ispresentduringthedepressurization process Any uncertainties should be addressed before proceeding...

Страница 7: ...ends of the lines must be round clean and free of any burrs 13 Place grommets in proper orientation onto line set with sufficient distance to braze joint 14 Insert the line set tubes into the coil tub...

Страница 8: ...coil case and furnace that were previously removed to install the indoor coil Refrigerant Charging These cased indoor coils are not factory charged with refrigerant It will be necessary to evacuate th...

Отзывы: