background image

3

1.  GENERAL INFORMATION

Standard cased coils are designed for upflow/
downflow applications or horizontal applications 
when  used  in  conjunction  with  our  horizontal 
drain pan kit (See page 5). Accessory kits are 
not  required  for  factory  ready  horizontal  coils. 
Coils are equipped with braze type refrigerant 

connections for easy installation.

Read the installation manual supplied 

with  the  outdoor  unit  for  refrigerant  line 
connection  procedure,  required  line  sizes, 

and other information pertaining to the system 
installation.

1.  Make certain that the air delivery of the 

furnace/air handler is adequate to handle 
the static pressure drop of the coil, filter, and 

duct work.

2.  Check the orifice size of the coil’s expansion 

device and confirm that it is suitable for 

application with the intended outdoor unit.

 

NOTE:

 Some coils employ a thermostatic 

expansion valve (TXV) as the metering 
device (See page 4).

H

20 

3

/

4

"

B

16 

5

/

8

"

W

A

3/4"

13

 

3

/

8

"

15

5

/

8

"

19 

3

/

4

"

Figure 1.

3.  Where precise forming of the refrigerant lines 

is required, a copper tubing bender designed 

for  the  size  lines  used  is  recommended. 
Avoid  sharp  bends  and  contact  of  the 
refrigerant lines with metal surfaces.

4.  Refrigerant  lines  should  be  wrapped  with

 

pressure sensitive neoprene or other 

suitable material where they pass through 
the raw edges of holes.

5.  Coil  must  be  level  for  proper  condensate

 

drainage.

NOTE:

  Optional cooling/heating equipment must 

be properly sized and installed in accordance 
with the furnace manufacturer’s specifications 
and approved recommendations. “Heating only” 

furnace air circulators may have to be replaced 

with  multi-speed  “Heating/Cooling”  blowers  to 
upgrade the air delivery (CFM) when an add-on 
coil is installed. Refer to Coil Specifications for 
recommended CFM and allow for pressure drop 

across the coil and filters.

Содержание C5B

Страница 1: ...tionsand orfurnace air handler markings before proceeding with installation of the coil These instructions are primarily intended to assist qualified individuals experienced in the proper installation...

Страница 2: ...izontal Furnace Horizontal Ready Coils for Horizontal Left Installation Horizontal Ready Coils for Horizontal Right Installation 4 Verify Pressurization 6 5 Refrigerant Line Connections 6 6 Completing...

Страница 3: ...tdoor unit NOTE Some coils employ a thermostatic expansion valve TXV as the metering device See page 4 H 20 3 4 B 16 5 8 W A 3 4 133 8 155 8 19 3 4 Figure 1 3 Wherepreciseformingoftherefrigerantlines...

Страница 4: ...63 913963 913963 913964 913964 913964 Extra Orifice in N A 0 053 for 1 5 ton condenser N A N A 0 053 for 1 5 ton condenser N A N A N A N A N A N A N A N A Coil Model 1 C5BA H T X24C A C5BA H T25C A C5...

Страница 5: ...the threaded holes of the horizontal drain pan If webbing is not removed the drain will not function properly and ceiling damage may occur 3 Insert a plug from the horizontal drain pan into the open a...

Страница 6: ...id direct face exposure or contact with valve when gas is escaping Always ensure adequate ventilation ispresentduringthedepressurization process Any uncertainties should be addressed before proceeding...

Страница 7: ...ends of the lines must be round clean and free of any burrs 13 Place grommets in proper orientation onto line set with sufficient distance to braze joint 14 Insert the line set tubes into the coil tub...

Страница 8: ...coil case and furnace that were previously removed to install the indoor coil Refrigerant Charging These cased indoor coils are not factory charged with refrigerant It will be necessary to evacuate th...

Отзывы: