Multi Variable Heat Pump WALL Mounted Type Indoor Unit
5
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L
≤
250m
(L
≤
820-1/5feet)
2×0.75~2×1.25
(2×AWG18~2×AWG16)
IEC
60227-5:2007
1. Total length of communication
line can't exceed 250m (820feet).
2. The cord shall be Circular cord
(the cords shall be twisted
together).
3. If unit is installed in or near
strong electromagnetic field, use
shielded wire.
3.2.2 Select communication line for indoor unit and indoor unit (outdoor unit)
Fig 3.2.2
Material Type
Total Length L (m/feet)
of Communication
Cable between Indoor
Unit and Indoor
(Outdoor) Unit
Wire size
(mm
2
/AWG)
Materi
al
Standa
rd
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L
≤
1000m
(L
≤
3280-5/6feet)
≥
2×0.75
(
≥
2×AWG18)
IEC
60227-5:
2007
1. If the wire diameter is enlarged to 2×1
mm
2
(2×AWG16), the total
communication line length can reach
1500 m (4900 feet).
2. The cord shall be Circular cord (the
cords shall be twisted together).
3. If unit is installed in or near strong
electromagnetic field , use shielded wire.
3.3 Electric Installation
Model
Power Supply
MCA(A)
MOP(A)
B-HW-2.2(07)-A3AK
208/230V-1ph-60Hz
1
15
B-HW-2.8(09)-A3AK
1
15
B-HW-3.6(12)-A3AK
1
15
B-HW-5.0(18)-A3AK
1
15
B-HW-7.1(24)-A3AK
1
15
(1)
Use copper wire only as unit’s power cord. Operating temperature should be within its rated value.
(2)
If the power cord is more than 15m (49 feet) long, proportionally increase the sectional area of power
cord to avoid overload.
(3)
Above selection requirements: Power cord size is based on BV single -core wire (2~4pc) at 40°C (104°F)
ambient temperature when laying across plastic pipe. Air switch is D type and used at 40°C (104°F). If
actual installation condition varies, please lower the capacity according to the specifications of power
cord and air switch provided by manufacturer.
(4)
Install cut-off device near the unit. The minimum distance between each stage of cut-off device should be
3mm(1/8 inch)(The same for both indoor unit and outdoor unit).
(5)
If the supply cord is damaged, it must be replaced by a qualified technician in order to avoid a hazard.