background image

9

Charging the Unit in AC mode

If the outdoor temperature is 65 degrees F or higher:

After completing the refrigerant line connections, leak 

checking the system, and evacuating the indoor section 

and all line connections (using proper methods), perform 

the following steps:

1. Determine the recommended charge addition (if applicable) 

for the system being installed. This information is in the 

unit’s QRD (Quick Reference Data sheet).

2. Calculate the amount of additional refrigerant needed for 

the line set length of the actual installation. This information 

is on the first page of the unit’s QRD (Quick Reference 

Data sheet).

3. Weigh in the additional charge amounts determined by 

step 1 and 2 above.

4. Adjust the charge to match the superheat (for fixed orifice 

systems) or subcooling (for TXV systems). There are three 

different resources for doing this:

a.)  The chargecalculator.com website. This will walk 

you through the charging process step by step.

b.)  The charging tables on the inside of the outdoor 

unit’s electrical box cover panel. These tables 

provide superheat targets for fixed orifice systems 

and subcooling targets for TXV systems. The system 

should be charged so that the measured superheat/

subcooling are within 1 degree F of the target listed 

in the table.

For fixed orifice systems:

•  If your measured superheat at the suction valve is 

LESS THAN

 the recommended superheat value 

in the table then 

REMOVE

 refrigerant.

•  If your measured superheat at the suction valve 

is 

GREATER THAN

 the recommended superheat 

value in the table then 

ADD

 refrigerant.

For TXV systems:

•  If your measured subcooling at the liquid valve is 

LESS THAN

 the recommended subcooling value 

in the table then 

ADD

 refrigerant.

•  If your measured subcooling at the liquid valve is 

GREATER THAN

 the recommended subcooling 

value in the table then 

REMOVE

 refrigerant.

c.)  The charging tables in the Supplemental Charging 

Information, can be found online in the literature 

library. The tables can also be accessed by scanning 

the QR code on the unit’s electrical panel. The 

pressures listed in these tables are for reference only 

and are to be used in troubleshooting a system. The 

system should be charged to match the superheat 

or subcooling targets as previously noted and not 

to match the system pressures. Follow the same 

procedure described in 4b above.

If the outdoor temperature is between 35 degrees F and 

65 degrees F:

After completing the refrigerant line connections, leak 

checking the system, and evacuating the indoor section 

and all line connections (using proper methods), perform 

the following steps:

1. Determine the recommended charge addition (if applicable) 

for the system being installed. This information is in the 

unit’s QRD (Quick Reference Data sheet).

2. Calculate the amount of additional refrigerant needed for 

the line set length of the actual installation. This information 

is on the first page of the unit’s QRD (Quick Reference 

Data sheet).

3. Weigh in the additional charge amounts determined by 

step 1 and 2 above.

4. Block off the discharge of the outdoor fan. 

NOTE:

 One half 

of the unit should be covered corner to corner as shown 

in 

Figure 4

.

5. With the unit in cooling mode, Adjust the charge to match 

the superheat (for fixed orifice systems) or subcooling (for 

TXV systems). There are two different resources for doing 

this:

a.)  The chargecalculator.com website. This will walk 

you through the charging process step by step.

b.)  The low ambient charging tables on the inside of 

the outdoor unit’s electrical box cover panel. These 

tables provide superheat targets for fixed orifice 

systems and subcooling targets for TXV systems. 

The system should be charged so that the measured 

superheat/subcooling are within 1 degree F of the 

target listed in the table.

For fixed orifice systems:

•  If your measured superheat at the suction valve is 

LESS THAN

 the recommended superheat value 

in the table then 

REMOVE

 refrigerant.

•  If your measured superheat at the suction valve 

is 

GREATER THAN

 the recommended superheat 

value in the table then 

ADD

 refrigerant.

For TXV systems:

•  If your measured subcooling at the liquid valve is 

LESS THAN

 the recommended subcooling value 

in the table then 

ADD

 refrigerant.

•  If your measured subcooling at the liquid valve is 

GREATER THAN

 the recommended subcooling 

value in the table then 

REMOVE

 refrigerant

NOTE

: One half of the unit should be covered corner to corner.

Figure 4. Blocked Off Outdoor Fan Discharge

Содержание 1SN18K

Страница 1: ...stallation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 AIR CO...

Страница 2: ...checkout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is de...

Страница 3: ...for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ve...

Страница 4: ...nds and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of...

Страница 5: ...quire modification to the expansion device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided e...

Страница 6: ...ccordance with the unit wiring diagram and the unit rating plate Connect the line voltage leads to the terminals on the contactor inside the control compartment Use only copper wire for the line volta...

Страница 7: ...al and Figure 3 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or...

Страница 8: ...erify that the thermostat is set to the stand by or off setting And the fan switch is set to automatic or off Start Up Procedures The thermostat s function mode should be set to OFF and the fan mode s...

Страница 9: ...troubleshooting a system The system should be charged to match the superheat or subcooling targets as previously noted and not to match the system pressures Follow the same procedure described in 4b a...

Страница 10: ...Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Da...

Страница 11: ...itable for 105 deg C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and...

Страница 12: ...llon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ord...

Отзывы: