background image

8

START UP & ADJUSTMENTS

Pre-Start Check List

 Verify that the outdoor unit is installed according to all 

instructions in this document.

 Verify that the indoor unit is appropriate for use with the 

refrigerant listed on the outdoor unit.  And that it has the 

proper design pressure for the outdoor unit equipment 

type.

  Verify the indoor unit and thermostat have been installed 

in accordance with that equipment’s instructions.

  Verify line voltage power leads are securely connected and 

that both indoor and outdoor units are properly grounded.

  Verify that the power supplied by branch circuits for both 

the indoor and outdoor equipment is:

•  the proper voltage for the equipment, and 

•  that the overcurrent protection device is properly 

sized, and 

•  that the supply wiring is the correct gauge.

  Verify that the low voltage and thermostat wiring are securely 

connected to the proper terminals for all equipment.

  Verify that the low voltage transformer has been properly 

connected with that unit’s instructions.

  Verify that the refrigerant line-set has been properly routed 

between the units, connected appropriately, is properly 

secured and protected from damage, and that it has the 

correct piping insulation installed.

  Verify that the refrigerant system and lines are leak free by 

inspection with a leak detector or the soap-bubble method.

  Verify that any attached indoor ducting has been properly 

installed and sealed.

 Verify that the indoor condensate drain line and trap are 

properly installed and functioning.

 Verify that all removable panels have been re-installed, 

and all cabinet enclosures and fan guards are secure.

  Verify that the air filters are clean and properly installed.

 Verify that the thermostat is set to the stand-by, or off 

setting.  And the fan switch is set to automatic or off.

Start-Up Procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the system.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan mode 

to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 

balanced air distribution. If insufficient air is detected, 

examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the blower 

stops running.

System Cooling

1. Set the thermostat’s system mode to COOL and the fan 

mode to AUTO. Gradually lower the thermostat temperature 

setpoint below room temperature and verify the outdoor 

unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 

and verify that it is cooler than ambient temperature. Listen 

for any unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

3. Verify HI and LO refrigerant pressures.

4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 

Verify the fan and compressor cycle off with the thermostat. 

NOTE:

 The blower should also stop unless fan mode is 

set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or electric 

heat) and indoor blower energize. Feel the air being 

circulated by the indoor blower and verify that it is warmer 

than ambient temperature. Listen for any unusual noises. 

If unusual sounds occur, determine the source of the noise 

and correct as necessary.

Содержание 1SN18K

Страница 1: ...stallation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 AIR CO...

Страница 2: ...checkout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is de...

Страница 3: ...for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ve...

Страница 4: ...nds and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of...

Страница 5: ...quire modification to the expansion device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided e...

Страница 6: ...ccordance with the unit wiring diagram and the unit rating plate Connect the line voltage leads to the terminals on the contactor inside the control compartment Use only copper wire for the line volta...

Страница 7: ...al and Figure 3 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or...

Страница 8: ...erify that the thermostat is set to the stand by or off setting And the fan switch is set to automatic or off Start Up Procedures The thermostat s function mode should be set to OFF and the fan mode s...

Страница 9: ...troubleshooting a system The system should be charged to match the superheat or subcooling targets as previously noted and not to match the system pressures Follow the same procedure described in 4b a...

Страница 10: ...Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Da...

Страница 11: ...itable for 105 deg C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and...

Страница 12: ...llon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ord...

Отзывы: