3
AIR CONDITIONER INSTALLATION
General Information
The *SA3BD4M series air conditioner is designed only
for outdoor rooftop or ground level installations. This unit
has been tested for capacity and efficiency in accordance
with AHRI Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and create
unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain mechanical
skills and tools.
Before You Install this Unit
√
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
√
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
√
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the
indoor unit's installation instructions for installation details.
√
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior
to installing the equipment at the job site. Verify coil fins
are straight. If necessary, comb fins to remove flattened
or bent fins. Claims for damage (apparent or concealed)
should be filed immediately with the carrier.
√
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all
instructions before installing the unit.
Packaging Removal
NOTE:
To prevent damage to the tubing connections, carefully
remove the carton and user’s manual from the equipment.
Discard the shipping carton.
Locating the Air Conditioner
• Survey the job site to determine the best location for
mounting the outdoor unit.
• Sufficient clearance for unobstructed airflow through the
outdoor coil must be maintained in order to achieve rated
for minimum clearances to
obstructions.
• Overhead obstructions (
), poorly ventilated areas,
and areas subject to accumulation of debris should be
avoided.
• The unit should not be placed under roofing or other
overhangs which are not guttered; that would allow water
or ice to fall into the unit’s discharge opening.
• Consideration should be given to availability of electric
power, service access, noise, and shade.
Clearance Requirements
• The general recommendation is for the units to be installed
with 18 inches of clearance on 3 sides and with 24 inches
Figure 1. Clearance Requirements
of clearance for the service access side to the unit’s service
panel.
• For installations that are space constrained, one side of the
unit, adjacent to the service panel, may have its air side
clearance reduced to a minimum of 6 inches. The other
side adjacent to the service panel requires 24 inches for
service access. The remaining two sides, at a minimum
shall require 12 inches of clearance.
• A minimum of 18 inches between two units must be
maintained for proper performance.
Ground Level
• The unit should be installed on a solid base, that is level
and located at least 2 inches above grade*. Note: It is
recommended that poured concrete mounting bases are
not be attached or adjacent to the building structure or
foundation.
Roof Mount
• The unit may only be installed on a structure that is capable
of supporting the total weight of the unit and its anchorage.
The support for the base of the unit may not slope more
than 1/8 inch per foot. The minimum clearance for the
base of the unit to the roof-line is 2 inches* for residential
applications.
*
Note on ground and roof clearances:
Heat pump and
other applications should account for the accumulation
of snow and raise the base of the unit accordingly. (At a
minimum, a 6 inch clearance is required.)
Accessory Mounting Kits
• Kits for other mounting methods and accessories can be
found in the technical sales literature for the unit. Or the
literature library on NortekHVAC.com.
24" for
Service Access
12" or 18”
See Note
12" or 18”
See Note
DO NOT
OBSTRUCT
TOP OF UNIT
NOTE:
Units require full perimeter clearances.
Installer must maintain 18” between two units.
18” Recommended.
(Minimum allowable clearance
of 6” to structure on
1 side of the unit only.)