background image

3

AIR CONDITIONER INSTALLATION

General Information

The *SA3BD4M series air conditioner is designed only 

for outdoor rooftop or ground level installations. This unit 

has been tested for capacity and efficiency in accordance 

with AHRI Standards and will provide many years of safe 

and dependable comfort, providing it is properly installed 

and maintained. Abuse, improper use, and/or improper 

maintenance can shorten the life of the appliance and create 

unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain mechanical 

skills and tools.

Before You Install this Unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

 Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 

and provided with circuit protection in accordance with 

local building codes. If there is any question concerning 

the power supply, contact the local power company.

 The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to the 

indoor unit's installation instructions for installation details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins 

are straight. If necessary, comb fins to remove flattened 

or bent fins. Claims for damage (apparent or concealed) 

should be filed immediately with the carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 

instructions before installing the unit.

Packaging Removal

NOTE:

 To prevent damage to the tubing connections, carefully 

remove the carton and user’s manual from the equipment. 

Discard the shipping carton.

Locating the Air Conditioner

• Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. See 

Figure 1

 for minimum clearances to 

obstructions.

•  Overhead obstructions (

Figure 1

), poorly ventilated areas, 

and areas subject to accumulation of debris should be 

avoided.

• The unit should not be placed under roofing or other 

overhangs which are not guttered; that would allow water 

or ice to fall into the unit’s discharge opening.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

Clearance Requirements

•  The general recommendation is for the units to be installed 

with 18 inches of clearance on 3 sides and with 24 inches 

Figure 1. Clearance Requirements

of clearance for the service access side to the unit’s service 

panel.

•  For installations that are space constrained, one side of the 

unit, adjacent to the service panel, may have its air side 

clearance reduced to a minimum of 6 inches.  The other 

side adjacent to the service panel requires 24 inches for 

service access.  The remaining two sides, at a minimum 

shall require 12 inches of clearance.

• A minimum of 18 inches between two units must be 

maintained for proper performance.

Ground Level

•  The unit should be installed on a solid base, that is level 

and located at least 2 inches above grade*.  Note: It is 

recommended that poured concrete mounting bases are 

not be attached or adjacent to the building structure or 

foundation.

Roof Mount

•  The unit may only be installed on a structure that is capable 

of supporting the total weight of the unit and its anchorage.  

The support for the base of the unit may not slope more 

than 1/8 inch per foot. The minimum clearance for the 

base of the unit to the roof-line is 2 inches* for residential 

applications.  

*

Note on ground and roof clearances:

 Heat pump and 

other applications should account for the accumulation 

of snow and raise the base of the unit accordingly.  (At a 

minimum, a 6 inch clearance is required.)

Accessory Mounting Kits

•  Kits for other mounting methods and accessories can be 

found in the technical sales literature for the unit.  Or the 

literature library on NortekHVAC.com.

24" for 

Service Access

12" or 18”

See Note

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE:

 Units require full perimeter clearances.

Installer must maintain 18” between two units.

18” Recommended.

(Minimum allowable clearance

of 6” to structure on

1 side of the unit only.)

Содержание 1SN18K

Страница 1: ...stallation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 AIR CO...

Страница 2: ...checkout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is de...

Страница 3: ...for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ve...

Страница 4: ...nds and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of...

Страница 5: ...quire modification to the expansion device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided e...

Страница 6: ...ccordance with the unit wiring diagram and the unit rating plate Connect the line voltage leads to the terminals on the contactor inside the control compartment Use only copper wire for the line volta...

Страница 7: ...al and Figure 3 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or...

Страница 8: ...erify that the thermostat is set to the stand by or off setting And the fan switch is set to automatic or off Start Up Procedures The thermostat s function mode should be set to OFF and the fan mode s...

Страница 9: ...troubleshooting a system The system should be charged to match the superheat or subcooling targets as previously noted and not to match the system pressures Follow the same procedure described in 4b a...

Страница 10: ...Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Da...

Страница 11: ...itable for 105 deg C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and...

Страница 12: ...llon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ord...

Отзывы: