Nortek 1RP24K Series Скачать руководство пользователя страница 9

9

or cooling. After short removed, defrost mode will be 

terminated when conditions are met.

•  Forced defrost can be maintained for up to 11 minutes by 

continuously maintaining the short across the test terminals. 

If held for over 11 minutes, the unit will stop and a flashing 

‘dF’ will be indicated on the board.

•  A continuous display of a fault code will indicate that the 

fault is still active.

•  A flashing fault code indicates that the fault has been 

corrected but remains in memory for troubleshooting 

purposes.

•  Multiple fault codes are listed in order from the most recent 

to the oldest. Only ten codes will be stored in memory.

•  Faults will remain in the board memory for seven days 

after the last fault is corrected.

•  Faults can be cleared from memory by shorting the test 

terminal momentarily while there is not a call for heating 

or cooling.

Charging the Unit in AC mode

If the outdoor temperature is 65 degrees F or higher:

After completing the refrigerant line connections, leak 

checking the system, and evacuating the indoor section 

and all line connections (using proper methods), perform 

the following steps:

1. Determine the recommended charge addition (if applicable) 

for the system being installed. This information is in the 

unit’s QRD (Quick Reference Data sheet).

2. Calculate the amount of additional refrigerant needed for 

the line set length of the actual installation. This information 

is on the first page of the unit’s QRD (Quick Reference 

Data sheet).

3. Weigh in the additional charge amounts determined by 

step 1 and 2 above.

4. Adjust the charge to match the superheat (for fixed orifice 

systems) or subcooling (for TXV systems). There are three 

different resources for doing this:

a.)  The chargecalculator.com website. This will walk 

you through the charging process step by step.

b.)  The charging tables on the inside of the outdoor 

unit’s electrical box cover panel. These tables 

provide superheat targets for fixed orifice systems 

and subcooling targets for TXV systems. The system 

should be charged so that the measured superheat/

subcooling are within 1 degree F of the target listed 

in the table.

For fixed orifice systems:

•  If your measured superheat at the suction valve is 

LESS THAN

 the recommended superheat value 

in the table then 

REMOVE

 refrigerant.

•  If your measured superheat at the suction valve 

is 

GREATER THAN

 the recommended superheat 

value in the table then 

ADD

 refrigerant.

For TXV systems:

•  If your measured subcooling at the liquid valve is 

LESS THAN

 the recommended subcooling value 

in the table then 

ADD

 refrigerant.

•  If your measured subcooling at the liquid valve is 

GREATER THAN

 the recommended subcooling 

value in the table then 

REMOVE

 refrigerant.

c.)  The charging tables in the Supplemental Charging 

Information, can be found online in the literature 

library. The tables can also be accessed by scanning 

the QR code on the unit’s electrical panel. The 

pressures listed in these tables are for reference only 

and are to be used in troubleshooting a system. The 

system should be charged to match the superheat 

or subcooling targets as previously noted and not 

to match the system pressures. Follow the same 

procedure described in 4b above.

If the outdoor temperature is between 35 degrees F and 

65 degrees F:

After completing the refrigerant line connections, leak 

checking the system, and evacuating the indoor section 

and all line connections (using proper methods), perform 

the following steps:

1. Determine the recommended charge addition (if applicable) 

for the system being installed. This information is in the 

unit’s QRD (Quick Reference Data sheet).

2. Calculate the amount of additional refrigerant needed for 

the line set length of the actual installation. This information 

is on the first page of the unit’s QRD (Quick Reference 

Data sheet).

3. Weigh in the additional charge amounts determined by 

step 1 and 2 above.

4. Block off the discharge of the outdoor fan. 

NOTE:

 One half 

of the unit should be covered corner to corner as shown 

in 

Figure 4

.

NOTE

: One half of the unit should be covered corner to corner.

Figure 4. Blocked Off Outdoor Fan Discharge

Table 2. Defrost Control Board Status Indicators

STATUS

INDICATOR

STATUS

TYPE

DIAGNOSTIC

DESCRIPTION

C1

Operating Status

Cooling, 1st Stage

C2

Operating Status

Cooling, 2nd Stage

H1

Operating Status

Heating, 1st Stage

H2

Operating Status

Heating, 2nd Stage

SC

Operating Status

Anti Short Cycle Timer

DF

Operating Status

Defrost

_.

Operating Status

Power on, no call for operation

01

Fault

Pressure switch, low

02

Fault

Pressure switch, high

03

Fault

Temperature Sensor, Ambient

04

Fault

Temperature Sensor, Coil

05

Fault

Board

OF

(FLASHING)

Input Error

Forced defrost - test short applied 

longer than 11 minutes

Содержание 1RP24K Series

Страница 1: ...mer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 HEAT PUMP INSTALLATION 3 General Information 3 Before You Install this Unit 3 Packaging Removal 3 Locating the Heat Pump 3 Clearance Requirements 3 Ground Level 3 Roof Mount 3 Accessory Mounting Kits 3 INSTALLATION VERIFICATION OF THE SYSTEMS EXPANSION DE...

Страница 2: ... the instructions provided with the equipment priortoperformingtheinstallationandoperationalcheckout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is designed for outdoor installations only and should be positioned as shown on page 3 IMPORTANT SAFETY INFORMATI...

Страница 3: ...ine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided The unit should not be placed under roofing or othe...

Страница 4: ...rs and connect them in accordance with the following 1 Inspect the outside of the couplings and ensure that they are free of any dirt or debris Clean if necessary 2 Removetheprotectivecapsandplugsfromthecouplingsto bejoined Inspecttheinteriorofthecoupling Ifnecessary clean the interior of the coupling with a clean soft lint free rag or cloth Ensure that o ring is in place and that the threads are ...

Страница 5: ... the refrigerant system to air to prevent accumulation of moisture and other contaminants CAUTION When connecting refrigerant line sets together it is highly recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Copper oxides internal to the system can damage the compressors bearings and seals block small orificesandmicrochannelsorothe...

Страница 6: ...n device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve An automatic high pressure switch is factory installed installed in these units and is located on the discharge l...

Страница 7: ... outdoor unit field wiring interfaces Figure 7 page 12 and Figure 8 page 13 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum o...

Страница 8: ...nepressureis530psigorgreater thentheHeatPump Mild Weather Control Kit is required to be installed on the system Alternately the control system could be configured to utilize the emergency or auxiliary heating means in order to maintain reliable system operation Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check t...

Страница 9: ...then REMOVE refrigerant If your measured superheat at the suction valve isGREATERTHANtherecommendedsuperheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table th...

Страница 10: ...iquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant If the outdoor temperature is below 35 degrees F After completing the refrigerant line connections leak checking the system and evacuating the indoor section and all line connecti...

Страница 11: ...d Figure 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipment without ...

Страница 12: ...s that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant d...

Страница 13: ...ound 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...allon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPO...

Отзывы: