Nortek 1RP24K Series Скачать руководство пользователя страница 3

3

HEAT PUMP INSTALLATION

General Information

The *SH3QE4M series Heat Pump is designed only for 

outdoor rooftop or ground level installations. This unit has been 

tested for capacity and efficiency in accordance with AHRI 

Standards and will provide many years of safe and dependable 

comfort, providing it is properly installed and maintained. 

Abuse, improper use, and/or improper maintenance can 

shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain mechanical 

skills and tools.

Before You Install this Unit

  The cooling and heating loads  of the area to be conditioned 

must be calculated and a system of the proper capacity 

selected. It is recommended that the area to be conditioned 

be completely insulated and vapor sealed.

 Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 

and provided with circuit protection in accordance with 

local building codes. If there is any question concerning 

the power supply, contact the local power company.

 Verify that the indoor thermostat and wiring is correct for 

the installation of these units and that any required unit 

accessories are on-hand before beginning the installation.

 The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to the 

indoor unit's installation instructions for installation details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins 

are straight. If necessary, comb fins to remove flattened 

or bent fins. Claims for damage (apparent or concealed) 

should be filed immediately with the carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 

instructions before installing the unit.

Packaging Removal

NOTE:

 To prevent damage to the tubing connections, carefully 

remove the carton and user’s manual from the equipment. 

Discard the shipping carton.

Locating the Heat Pump

• Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. See 

Figure 1

 for minimum clearances to 

obstructions.

•  Overhead obstructions (

Figure 1

), poorly ventilated areas, 

and areas subject to accumulation of debris should be 

avoided.

• The unit should not be placed under roofing or other 

overhangs which are not guttered; that would allow water 

or ice to fall into the unit’s discharge opening.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

Clearance Requirements

•  The general recommendation is for the units to be installed 

with 18 inches of clearance on 3 sides and with 24 inches 

Figure 1. Clearance Requirements

of clearance for the service access side to the unit’s service 

panel.

•  For installations that are space constrained, one side of the 

unit, adjacent to the service panel, may have its air side 

clearance reduced to a minimum of 6 inches.  The other 

side adjacent to the service panel requires 24 inches for 

service access.  The remaining two sides, at a minimum 

shall require 12 inches of clearance.

• A minimum of 18 inches between two units must be 

maintained for proper performance.

Ground Level

•  The unit should be installed on a solid base that is level 

and located at least 2 inches above grade*. Note: It is 

recommended that poured concrete mounting bases 

are not attached or adjacent to the building structure or 

foundation.

Roof Mount

•  The unit may only be installed on a structure that is capable 

of supporting the total weight of the unit and its anchorage.  

The support for the base of the unit may not slope more 

than 1/8 inch per foot. The minimum clearance for the 

base of the unit to the roof-line is 2 inches* for residential 

applications.  

*

Note on ground and roof clearances:

 Heat pump and 

other applications should account for the accumulation 

of snow and raise the base of the unit accordingly.  (At a 

minimum, a 6 inch clearance is required.)

Accessory Mounting Kits

•  Kits for other mounting methods and accessories can be 

found in the technical sales literature for the unit.  Or the 

literature library on NortekHVAC.com.

24" for 

Service Access

12" or 18”

See Note

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE: Units require full perimeter clearances.

Installer must maintain 18” between two units.

18” Recommended.

(Minimum allowable clearance

of 6” to structure on

1 side of the unit only.)

Содержание 1RP24K Series

Страница 1: ...mer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 HEAT PUMP INSTALLATION 3 General Information 3 Before You Install this Unit 3 Packaging Removal 3 Locating the Heat Pump 3 Clearance Requirements 3 Ground Level 3 Roof Mount 3 Accessory Mounting Kits 3 INSTALLATION VERIFICATION OF THE SYSTEMS EXPANSION DE...

Страница 2: ... the instructions provided with the equipment priortoperformingtheinstallationandoperationalcheckout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is designed for outdoor installations only and should be positioned as shown on page 3 IMPORTANT SAFETY INFORMATI...

Страница 3: ...ine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided The unit should not be placed under roofing or othe...

Страница 4: ...rs and connect them in accordance with the following 1 Inspect the outside of the couplings and ensure that they are free of any dirt or debris Clean if necessary 2 Removetheprotectivecapsandplugsfromthecouplingsto bejoined Inspecttheinteriorofthecoupling Ifnecessary clean the interior of the coupling with a clean soft lint free rag or cloth Ensure that o ring is in place and that the threads are ...

Страница 5: ... the refrigerant system to air to prevent accumulation of moisture and other contaminants CAUTION When connecting refrigerant line sets together it is highly recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Copper oxides internal to the system can damage the compressors bearings and seals block small orificesandmicrochannelsorothe...

Страница 6: ...n device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve An automatic high pressure switch is factory installed installed in these units and is located on the discharge l...

Страница 7: ... outdoor unit field wiring interfaces Figure 7 page 12 and Figure 8 page 13 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum o...

Страница 8: ...nepressureis530psigorgreater thentheHeatPump Mild Weather Control Kit is required to be installed on the system Alternately the control system could be configured to utilize the emergency or auxiliary heating means in order to maintain reliable system operation Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check t...

Страница 9: ...then REMOVE refrigerant If your measured superheat at the suction valve isGREATERTHANtherecommendedsuperheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table th...

Страница 10: ...iquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant If the outdoor temperature is below 35 degrees F After completing the refrigerant line connections leak checking the system and evacuating the indoor section and all line connecti...

Страница 11: ...d Figure 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipment without ...

Страница 12: ...s that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant d...

Страница 13: ...ound 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...allon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPO...

Отзывы: