Nortek 1RP24K Series Скачать руководство пользователя страница 11

11

Figure 5. Panel Removal

DETAIL A

DETAIL B

Figure 6. Panel Installation

HEAT PUMP MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

The unit may have more than one electrical 

supply.

Proper maintenance is important to achieve optimum 

performance from the Heat Pump. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning of 

each heating and cooling season, or more frequently if 

required.

•  Inspect the condensate drains in the units basepan and 

the outdoor coil at the beginning of each cooling season. 

Remove any debris. Clean the outdoor coil and louvers 

as necessary using a mild detergent and water. Rinse 

thoroughly with water.

•  To access the outdoor coil on units equipped with louvered 

panels, refer to 

Figure 5

 for panel removal and 

Figure 6

 

for panel installation.

• Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

•  Do not attempt to add additional oil or grease to motors 

unequipped with oil tubes or grease fittings.  Most outdoor 

unit motors are manufactured with sealed, permanently 

lubricated bearings that are designed for the life of the 

equipment without maintenance.

•  The compressor is hermetically sealed and shipped from 

the factory with the proper oil charge for most installations.  

Lubricating oil should only be added by trained personnel 

and is typically only required for long line-sets or tall riser 

applications.

Panel Removal

1. Remove screws securing the panel.

2. Slide the panel up towards the top pan in order to clear 

the bottom flange from the base pan. See 

Figure 5

.

3. Swing the bottom of the panel out and pull the panel down 

to remove it from the unit.

Panel Installation

1. Insert the top corners of side panel flanges into the corner 

post channels as shown in Detail A in 

Figure 6

.

2. Slide the panel up into the top pan. (You may need to push 

on the center of the panel at the top in order to clear the 

top pan edge).

3. Swing the panel in and push down until the panel is resting 

on the top edge of the base pan wall as shown in Detail 

B.

4. Install screws into the panel to secure it to the unit.

Содержание 1RP24K Series

Страница 1: ...mer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 HEAT PUMP INSTALLATION 3 General Information 3 Before You Install this Unit 3 Packaging Removal 3 Locating the Heat Pump 3 Clearance Requirements 3 Ground Level 3 Roof Mount 3 Accessory Mounting Kits 3 INSTALLATION VERIFICATION OF THE SYSTEMS EXPANSION DE...

Страница 2: ... the instructions provided with the equipment priortoperformingtheinstallationandoperationalcheckout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is designed for outdoor installations only and should be positioned as shown on page 3 IMPORTANT SAFETY INFORMATI...

Страница 3: ...ine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided The unit should not be placed under roofing or othe...

Страница 4: ...rs and connect them in accordance with the following 1 Inspect the outside of the couplings and ensure that they are free of any dirt or debris Clean if necessary 2 Removetheprotectivecapsandplugsfromthecouplingsto bejoined Inspecttheinteriorofthecoupling Ifnecessary clean the interior of the coupling with a clean soft lint free rag or cloth Ensure that o ring is in place and that the threads are ...

Страница 5: ... the refrigerant system to air to prevent accumulation of moisture and other contaminants CAUTION When connecting refrigerant line sets together it is highly recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Copper oxides internal to the system can damage the compressors bearings and seals block small orificesandmicrochannelsorothe...

Страница 6: ...n device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve An automatic high pressure switch is factory installed installed in these units and is located on the discharge l...

Страница 7: ... outdoor unit field wiring interfaces Figure 7 page 12 and Figure 8 page 13 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum o...

Страница 8: ...nepressureis530psigorgreater thentheHeatPump Mild Weather Control Kit is required to be installed on the system Alternately the control system could be configured to utilize the emergency or auxiliary heating means in order to maintain reliable system operation Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check t...

Страница 9: ...then REMOVE refrigerant If your measured superheat at the suction valve isGREATERTHANtherecommendedsuperheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table th...

Страница 10: ...iquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant If the outdoor temperature is below 35 degrees F After completing the refrigerant line connections leak checking the system and evacuating the indoor section and all line connecti...

Страница 11: ...d Figure 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipment without ...

Страница 12: ...s that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant d...

Страница 13: ...ound 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...allon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPO...

Отзывы: