Nortek 1RP24K Series Скачать руководство пользователя страница 8

8

START UP & ADJUSTMENTS

Pre-Start Check List

 Verify that the outdoor unit is installed according to all 

instructions in this document.

 Verify that the indoor unit is appropriate for use with the 

refrigerant listed on the outdoor unit.  And that it has the 

proper design pressure for the outdoor unit equipment 

type.

  Verify the indoor unit and thermostat have been installed 

in accordance with that equipment’s instructions.

  Verify line voltage power leads are securely connected and 

that both indoor and outdoor units are properly grounded.

  Verify that the power supplied by branch circuits for both 

the indoor and outdoor equipment is:

•  the proper voltage for the equipment, and 

•  that the overcurrent protection device is properly 

sized, and 

•  that the supply wiring is the correct gauge.

  Verify that the low voltage and thermostat wiring are securely 

connected to the proper terminals for all equipment.

  Verify that the low voltage transformer has been properly 

connected with that unit’s instructions.

  Verify that the refrigerant line-set has been properly routed 

between the units, connected appropriately, is properly 

secured and protected from damage, and that it has the 

correct piping insulation installed.

  Verify that the refrigerant system and lines are leak free by 

inspection with a leak detector or the soap-bubble method.

  Verify that any attached indoor ducting has been properly 

installed and sealed.

 Verify that the indoor condensate drain line and trap are 

properly installed and functioning.

 Verify that all removable panels have been re-installed, 

and all cabinet enclosures and fan guards are secure.

  Verify that the air filters are clean and properly installed.

 Verify that the thermostat is set to the stand-by, or off 

setting.  And the fan switch is set to automatic or off.

Start-Up Procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 
disconnects to energize the system.

 WARNING:

This unit is equipped with a crankcase heater. 

Allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

Operating Temperatures

This equipment has been designed to operate for a large range 

of ambient conditions, however: running the heat-pump in 

heating mode, at higher than 70°F ambient temperatures may 

require the use of a 

Heat Pump Mild Weather Control Kit

If an application is expected to require heating operation during 

mild ambient temperatures the systems liquid line pressures 

should be inspected during these periods of operation. If the 

liquid line pressure is 530 psig or greater, then the Heat Pump 

Mild Weather Control Kit is required to be installed on the 

system. Alternately, the control system could be configured 

to utilize the emergency or auxiliary heating means in order 

to maintain reliable system operation.  

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan mode 

to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 

balanced air distribution. If insufficient air is detected, 

examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the blower 

stops running.

Short Cycle Protection

1. Set the thermostat system mode to COOL. Observe the 

temperature setting of the thermostat and gradually raise 

the set-point temperature until the unit de-energizes.

2. Immediately lower the set point temperature of the 

thermostat to its original setting and verify that the indoor 

blower is energized and outdoor unit remains de-energized.

3. After approximately 5 minutes, verify the outdoor unit 

energizes and the temperature of the discharge air is 
cooler than the room temperature.

System Cooling

1. Set the thermostat’s system mode to COOL and the fan 

mode to AUTO. Gradually lower the thermostat temperature 

setpoint below room temperature and verify the outdoor 

unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 

and verify that it is cooler than ambient temperature. Listen 

for any unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

3. Verify HI and LO refrigerant pressures.

4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 

Verify the fan and compressor cycle off with the thermostat. 

NOTE:

 The blower should also stop unless fan switch is 

set to the ON position.

System Heating

1. Set the thermostat's system mode to HEAT and the 

temperature mode to below room temperature.

2. Verify the outdoor unit and indoor fan stop running. After 

5 minutes, increase the temperature on the thermostat to 

it's maximum setting.

3. Verify the outdoor unit and indoor blower energize. Feel 

the air being circulated by the indoor blower and verify 

that it is warmer than ambient temperature. Listen for any 

unusual noises. If unusual sounds occur, determine the 

source of the noise and correct as necessary.

Defrost Control Board Test Pins

•  Verify the Status Indicator (on the control board) against 

the codes listed in 

Table 2 (page 9)  

to determine proper 

diagnostic description.

•  Terminals ‘R’ and ‘C’ must have 18-30 VAC present between 

them for proper board operation.

•  Board anti-short cycle timer can be bypassed by shorting 

the test terminals for less than 1 second while there is a 

call for heating or cooling.

•  Forced defrost enabled when shorting the test terminals for 

more than three seconds while there is a call for heating 

Содержание 1RP24K Series

Страница 1: ...mer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 HEAT PUMP INSTALLATION 3 General Information 3 Before You Install this Unit 3 Packaging Removal 3 Locating the Heat Pump 3 Clearance Requirements 3 Ground Level 3 Roof Mount 3 Accessory Mounting Kits 3 INSTALLATION VERIFICATION OF THE SYSTEMS EXPANSION DE...

Страница 2: ... the instructions provided with the equipment priortoperformingtheinstallationandoperationalcheckout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is designed for outdoor installations only and should be positioned as shown on page 3 IMPORTANT SAFETY INFORMATI...

Страница 3: ...ine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided The unit should not be placed under roofing or othe...

Страница 4: ...rs and connect them in accordance with the following 1 Inspect the outside of the couplings and ensure that they are free of any dirt or debris Clean if necessary 2 Removetheprotectivecapsandplugsfromthecouplingsto bejoined Inspecttheinteriorofthecoupling Ifnecessary clean the interior of the coupling with a clean soft lint free rag or cloth Ensure that o ring is in place and that the threads are ...

Страница 5: ... the refrigerant system to air to prevent accumulation of moisture and other contaminants CAUTION When connecting refrigerant line sets together it is highly recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Copper oxides internal to the system can damage the compressors bearings and seals block small orificesandmicrochannelsorothe...

Страница 6: ...n device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve An automatic high pressure switch is factory installed installed in these units and is located on the discharge l...

Страница 7: ... outdoor unit field wiring interfaces Figure 7 page 12 and Figure 8 page 13 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum o...

Страница 8: ...nepressureis530psigorgreater thentheHeatPump Mild Weather Control Kit is required to be installed on the system Alternately the control system could be configured to utilize the emergency or auxiliary heating means in order to maintain reliable system operation Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check t...

Страница 9: ...then REMOVE refrigerant If your measured superheat at the suction valve isGREATERTHANtherecommendedsuperheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table th...

Страница 10: ...iquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant If the outdoor temperature is below 35 degrees F After completing the refrigerant line connections leak checking the system and evacuating the indoor section and all line connecti...

Страница 11: ...d Figure 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipment without ...

Страница 12: ...s that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant d...

Страница 13: ...ound 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...allon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPO...

Отзывы: