HD272 Installation Instructions
27
Set the CLOSED Position Limit for PULL-TO-OPEN
Installation
Your transmitter must be able to operate the gate. If not see, "Personalize Your Transmitter Setting on page 20.
NOTE: The OPEN limit is when the opener is fully retracted and the gate is in the full open position. The open limit
setting can only be adjusted by moving the gate bracket. To achieve the optimum closed position, you must adjust the
CLOSED limit setting:
Step 1
Remove the Control Box Cover. Make sure the Control Box switch is ON and that the gate is in the OPEN POSITION (arms fully
retracted).
Step 2
Press and HOLD the 2nd opener JOG CLOSE button on the control board and be prepared to RELEASE the button when the gate
reaches the desired closed position/limit. Use the JOG OPEN and CLOSE buttons to "fine tune" the gate position if necessary.
Step 3
Press and HOLD the 1st opener JOG CLOSE button on
the control board and be prepared to RELEASE the button
when the gate reaches the desired closed position/limit. Use
the JOG OPEN and CLOSE buttons to "fine tune" the gate
position if necessary.
Step 4
With the gates in the desired closed positions, PRESS and
HOLD the SET LIMIT button until the alarm and RED SET
LIMIT light turn on, then release the button.
NOTE:
The opener must be extended more than 4 inches to
set limits.
Step 5
Press the transmitter button once (within 5 feet of the control board) and allow the gates to fully open. The alarm will beep once
when both gates reach the OPEN LIMIT. This indicates the limits for both arms are programmed in memory.
Step 6
Press the transmitter button and allow the gates to fully close to verify that they stop at the desired positions. Repeat Steps 2-5 if
correction is needed.
NOTE:
If the gate stops and reverses you may need to adjust the Stall Force (see next page).
Step 7
After CLOSED and OPEN limits are set to the desired positions, operate the gate through four complete open and close cycles.
This will automatically measure and configure the gate's force set up.
MIN
MAX OFF
REMOVE JUMPER FOR
PUSH TO OPEN OPTION
120
SEC.
STALL FORCE
OPEN < JOG > CLOSE
PWR.
SET
LIMIT
1st OPR.
2nd OPR.
STATUS
AUTO CLOSE
FIRST Opener
JOG Buttons
SET LIMIT Button
SET LIMIT Light
SECOND Opener
JOG Buttons