39 |
Operation
On/Off or Modulating Control (J10)
The RH2 output can be controlled by either an On/Off or a modulating humidistat. To set the
RH2 to operate with a modulating humidistat, remove Jumper J10. (Factory setting = jumper
Installed , On/Off operation)
J10 Removed
– Modulating operation, the controller monitors the demand signal on
terminal point 4 of the control terminal strip and adjusts humidifier output to match it.
J10 Installed
- The RH2 is configured for On/Off operation. The controller will ignore any
modulating signals even if they are connected.
Modulation Offset (J13)
The RH2 controller can be configured to work with a modulating humidistat with 4-20 mA or 2-
10 VDC output. Modulation offset can be configured with jumper 13. (Factory setting = Jumper
Removed, 0-10 VDC or 0-20 mA control signal)
J13 Removed
– Controller is configured for a 0-10 VDC or 0-20 mA control signal.
J13 Installed
– Controller is configured for a 2-10 VDC or 4-20 mA control signal.
For mA control a 500
register is required between terminals 3 and 4 on the low voltage
control terminal.
Table 6: Control Jumper Configuration
Resulting Control
J10
J13
On/Off
Installed
No Affect
Modulating 0-10 VDC or 0-20 mA
Removed
Removed
Modulating 2-10 VDC or 4-20 mA
Removed
Installed
Ground Fault Interrupt (GFI) (J15)
Ground current leakage can occur when the humidifier performs drains. With jumper J15 the
RH2 can be configured to turn off the power to the electrodes whenever a drain takes place.
J15 Removed
– The power relay is on during drains to control cylinder water concentration.
J15 Installed
– The power relay is turned off during drains to control cylinder water
concentration.
Содержание RH2
Страница 9: ...Installation 6 Typical RH2 Installation Figure 3 Typical Humidifier Installation 2 ...
Страница 22: ...19 Installation On Off Control Wiring Figure 18 On Off Controls Figure 19 Digital On Off Humidistat ...
Страница 23: ...Installation 20 Modulating Control Wiring Figure 20 Modulating Controls Figure 21 Modulating Control Wiring ...
Страница 33: ...Start Up 30 ...
Страница 38: ...35 Operation Humidifier Schematic Figure 29 Humidifier Schematic ...
Страница 56: ...53 Troubleshooting RH2 Wiring Diagram ...
Страница 60: ...57 Spare Parts ...