10-40
Page 53
2008-12-03
4.0 PRODUCT SPECIFICATIONS
4.1 TECHNICAL DATA
MHB FLOW
MHTC FLOW
MHB
REFLOW
MHTC
REFLOW
Control
Humidistat Total
Controller
Control MHB
Total Controller
Control supply charge
120 VAC /
60 Hz
120 VAC /
60 Hz
120 VAC /
60 Hz
120 VAC /
60 Hz
Circulation pump supply voltage
---
---
120 VAC/60 Hz
Control signals
Potential
free contact
of an
external
humidistat /
thermostat
0…5 VDC
1…5 VDC
0…10 VDC
2…10 VDC
0…16 VDC
3.2…16 VDC
0..20 mA
4..20 mA
Potential
free contact
of an
external
humidistat /
thermostat
0…5 VDC
1…5 VDC
0…10 VDC
2…10 VDC
0…16 VDC
3.2…16 VDC
0..20 mA
4..20 mA
Control characteristics
On/Off
Control Step
On/Off Control
Step
Control accuracy
Control accuracy depends on air conditions, control distance,
water quality and probably on the number of On/Off cycles.
Max. admissible air speed above
humidification boxes
3.8 m/s / 750 fpm (4.5 m/s / 885 fpm with 4” (100 mm) mist
eliminator, 5.5 m/s
Water supply
R ¾” outside thread
Water drain
1.5" PVC (1.66" (42 mm) OD)
outside diameter of tube
Admissible water supply pressure
Admissible water temperature
41-113ºF (5-45ºC)
Water quality
Tap water,
Reverse Osmosis,
softened or fully demineralized water.
Pressure drop
Typically 0.44 IWC @ 500 fpm, 90% rh
Admissible ambient temperature (Control
unit)
34…104ºF
(1…40ºC)
34…104ºF
1…40ºC
34…104ºF
1…40ºC
34…104ºF
1…40ºC
Admissible ambient humidity (Control unit)
Max. 75% rh
Max. 75% rh
Max. 75% rh
Max. 75% rh
Degree of protection of Control unit
Degree of protection of pump, valves, etc.
Fire classification of humidification medium
UL 900 Class 1
Accessories
Supply valve connection (24V)
S S S S
Drain water connection (24 V)
S S
Duct humidistat
y
y
y
y
Room humidistat
y
y
y
y
Duct humidity sensor
y
y
Room humidity sensor
y
y
Remote indication PCB
On/Error/Maintenance/Humidification
S S S
Options
UV water treatment
y
y
Drain valve (
24VAC
)
S S
Conductivity monitoring
y
y
Nortec Links BMS Interface
y
y
Nortec OnLine Web Control
y
y
y
y
S = Standard Equipment
y
= Option
Содержание MH Series
Страница 1: ...2544832 A MH Series EVAPORATIVE HUMIDIFIER COOLER Installation Manual TM ...
Страница 5: ...10 00 Page 1 2008 12 03 10 00 INTRODUCTION ...
Страница 21: ...10 10 Page 17 2008 12 03 10 10 INSTALLATION ...
Страница 37: ...10 20 Page 33 2008 12 03 10 20 PLUMBING ELECTRICAL INSTALLATION ...
Страница 42: ...10 20 Page 38 2008 12 03 1 3 3 Wiring Diagram Nortec MH Flow Figure 7 Wiring Diagram MH Flow ...
Страница 43: ...10 20 Page 39 2008 12 03 1 3 4 Wiring Diagram Nortec MH Reflow Figure 8 Wiring Diagram MH Reflow ...
Страница 44: ...10 20 Page 40 2008 12 03 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...10 30 Page 41 2008 12 03 10 30 OPERATION ...
Страница 48: ...10 30 Page 44 2008 12 03 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 49: ...10 40 Page 45 2008 12 03 10 40 MAINTENANCE TROUBLESHOOTING ...