background image

BLOWER PACK OPERATION

1.

Blower packs are an optional accessory used
to directly distribute steam to localized areas
or in structures that do not have a built-on air
distribution system.

2.

Blower packs are available for remote
mounting or built-on and are field piped to the
humidifier. (Built on Blower Packs are
available with NHTC & NHPC humidifiers
only.)

3.

All blower packs consist of a steel cabinet
containing; blower/motor powered by a 115
Vac single phase supply (208, 277, 440-480
and 550-600 Vac version available), plastic
steam distribution, adjustable air supply.
Control thermostat, mounted on the steam
distributor, starts the fan when steam is
generated.

4.

Refer to Overhead and Frontal Clearance
table for blower pack requirements.
Minimum clearance for the sides of the unit is
4 feet.

5.

Steam distributors on blower packs have hot
surfaces that could result in burns if touched.
If space allows, we recommend mounting at
least 8 feet above the floor (see Figure #2).

6.

Do not use blower packs as ducted blowers.
The air volume from a blower pack is not
sufficient to absorb the steam generated in
the confines of a duct system.

7.

It is recommended that balancing valves be
used on the steam supply lines to multiple
blower packs for equal loading.

REMOTE MOUNTED BLOWER PACKS

- WALL MOUNTING

1.

Steam and condensate line connections are
on the bottom of the blower pack. The
condensate connection is 3/8” and the steam
lines are 7/8” or 1 ½” depending. The knock
out for the appropriate steam connection
must be removed prior to mounting on the
wall. To remove knock out place unit on its
side, on a soft surface, and with a hammer
and a piece of pipe or screwdriver knock out
center of the steam inlet connection.

2.

To wall mount the Remote Blower Pack use
2 #12 x 3” long wood screws, supplied by
others. These screws must be fastened
securely on a 2 x 4 wood stud or equivalent
support. If any spacer material is used
between the bracket and the structural
material such as drywall, increase the
fastener accordingly. In addition, install a
single field supplied fastener in the center
hole in the back of the unit to prevent the unit
from being bumped off the support screws.

- 1 -

Power And
Control
Wiring

Optional
Built-On
Blower Pack

Single
Circuit
Humidifier

Built-In
Supply Air
Grille

Built-In Steam
Distributor

Figure #1

NHTC/NHPC Series Humidifier with Built-on

Blower Packs

Side

Wall

Condensate

Front

Steam

Power To Blower Pack

Control Wiring

From Humidifier

1” (2.5 cm)

Distributor

Figure #2

Blower Pack

Содержание BLOWER PACKS

Страница 1: ...WER PACKS All Atmospheric Humidifiers Installation Troubleshooting and Exploded Views IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner Form 07 239 1506261 ...

Страница 2: ......

Страница 3: ... WALL MOUNTING 1 REMOTE MOUNTED BLOWER PACKS STEAM LINE 2 CONDENSATE RETURN LINES 3 PRIMARY VOLTAGE CONNECTION 3 PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACK 4 BLOWER PACK CLEARANCES AND DIMENSIONS 5 EXPLODED VIEW OF THE BLOWER PACK 6 7 WIRING DIAGRAM 8 ...

Страница 4: ......

Страница 5: ...ed that balancing valves be used on the steam supply lines to multiple blower packs for equal loading REMOTE MOUNTED BLOWER PACKS WALL MOUNTING 1 Steam and condensate line connections are on the bottom of the blower pack The condensate connection is 3 8 and the steam lines are 7 8 or 1 depending The knock out for the appropriate steam connection must be removed prior to mounting on the wall To rem...

Страница 6: ...s This will also reduce the back pressure and avoid the need to install an extended water trap 5 Ensure that the steam hose does not kink or sag The steam hose becomes more flexible when hot The hose should be supported to prevent water traps Only use steam hose for connection or steam line runs of 5 feet or less See Figure 4 6 To ensure odor free steam always use NORTEC steam hose Check steam hos...

Страница 7: ...ng of condensate return lines Condensate that accumulates in trap will prevent possibility of steam escaping Depth of the trap must be equal or more than 3 76 mm See Figure 6 3 Ensure the trap is 3 minimum under the blower pack and as close to the floor drain as possible PRIMARY VOLTAGE CONNECTION 1 All blower packs for SE and GS unit are wired by others to be powered by an independent circuit 2 A...

Страница 8: ...TAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACK 1 All blower packs are wired by factory if built on and to be powered from the humidifier 2 All built on blower packs are factory wired to the humidifier Primary voltage wiring to the humidifier as described in electrical primary voltage supply wiring is all that is required to power the humidifier and blower packs 4 ...

Страница 9: ...6 91 42 106 48 122 42 106 48 122 Min Front Clearance Inches cm 30 76 30 76 36 91 72 183 84 213 144 366 156 396 144 366 156 396 Remote mounted only Four remote mounted blower packs are recommended on the 200 model Nominal conditions 72 F 35 RH OverheadAnd Frontal Clearances For Blower Packs Note Add 8 70 22 cm to the over all unit height for BOBP for NHTC NHPC Only Blower Pack Weight 120V model 12 ...

Страница 10: ... Packs Installation and Exploded Views 7 22 14 8 3 18 19 2 11 13 15 16 NOTE ITEMS 30 AND 31 NOT SHOWN ITEM 30 CAN REPLACE ITEM 18 AND ITEM 31 CAN REPLACE ITEM 10 IN DIFFERENT WORKING CONFIGURATIONS 9 10 1 20 4 5 6 12 25 17 24 27 28 26 23 21 29 ...

Страница 11: ...ributor plastic Blower Pack 1 13 2522178 Distributor Faceplate Blower Pack 1 14 1475005 Thermostat O Ring 1 15 1073005 Thermostat Control Non Reset 1 16 2524056 Hex Nut 2 56 Steel Zn plated 2 17 2522176 Cabinet Fan Housing Blowerpack 1 18 2522065 Fan Box 115V 110CFM 120x120x38mm 3 19 1504281 Fan cover 4in 6 20 1708808 Hex Nut 10 32 SS 8 21 2524080 Screw Selftapping lin 10 32 Philips Flat Head 24 2...

Страница 12: ...LOWER PACK SPECIFICATION LABEL FOR APPROPRIATE VOLTAGE BLOWER PACK LV TERMINAL BLOCK ON OFF LOOP TO BE WIRED TO HUMIDIFIER WITH OTHER ON OFF CONTROLS IN SERIES S STEP DOWN TRANSFORMER Not required for 115V Model S 0 75A FUSES S S 1 A FUSES Not required for 115V Model 115 VAC BLOWER PACK FAN KIT Orange 550 600V Yellow 440 480V Brown 277V Red 230V Black 208V White Common Transformer Primary Supply C...

Страница 13: ...implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY THE COMPANY s limited warranty on accessories not of AXAIR NORTEC s manufacture such as controls humidistats pumps et...

Страница 14: ......

Страница 15: ...WMH COMPANY www humidity com U S A AxAir NORTEC Inc 826 Proctor Avenue Ogdensburg New York 13669 CANADA AxAir NORTEC Ltd 2740 Fenton Road Ottawa ON K1T 3T7 1 866 NORTEC 1 Fax 613 822 7964 J xl ir Nortec aWMH Company ISO IJ ...

Отзывы: