For electric humidifiers (NHTC & NHPC only)
using a small size blower pack (<30 lbs/hr),
steam lines require 7/8” O.D. (Nominal ¾”)
copper tubing. For steam runs longer than
20 ft, use insulated nominal 1” copper to
ensure draining of condensate.

9.

When using the GS, SE, NHDI/NHSC
Humidifiers and RO / DI water supply, all
steam lines should be in stainless steel.

10.

Do not use plastic pipe for steam distribution
or hose other than NORTEC supplied.
Substitution will void warranty.

11.

If steam line is routed below the blower pack,
or if the blower pack is lower than the
humidifier, a condensate trap “tee” will be
required to remove water at this low point.
Run the condensate from the trap to the
nearest drain lower than the blower pack.
See Figure #5.

12. Do not run the steam line more than 1 foot

per lb/hr output. Example, 10 lbs/hr should
not have a steam run longer than 10 feet. If
long runs are unavoidable, the humidifier
should be sized larger to compensate for
condensate losses and insulated stainless
steel or copper should definitely be used.

CONDENSATE RETURN LINES

1.

NORTEC blower packs have built-in
connections for draining off condensate.
These condensate lines must be connected
to the nearest floor drain, back to the unit
(NHTC & NHPC, NHSC/DI only) or a
condensate pump when using short
condensatel runs. (Available from unit).

2.

Always incorporate a trap in routing of
condensate return lines. Condensate that
accumulates in trap will prevent possibility of
steam escaping. Depth of the trap must be
equal or more than 3” (76 mm) See Figure
#6.

3.

Ensure the trap is 3’ minimum under the
blower pack and as close to the floor drain as
possible.

PRIMARY VOLTAGE CONNECTION

1.

All blower packs for SE and GS unit are
wired by others to be powered by an
independent circuit.

2.

A control thermostat, mounted on the steam
distributor, cc starts the fan when steam is
generated.

3.

NH Series remote mounted blower packs
wired to a humidifier or independent circuit
require field wiring between two primary
voltage terminal blocks and two low voltage
control (class 1 circuit wiring required)
terminal strips; one of each located in
humidifier and remote blower pack cabinet.
To properly access the primary block on the
humidifier, it may be necessary to remove
the top. To connect the primary and control
(class 1 circuit wiring required) wiring, the
wiring is fed through the grommet provided in
the bottom of the blower pack.

4.

Field wiring of remote blower packs must
conform to national and local electrical
codes. Refer to wiring diagram supplied at
the back of this manual (See page 9).

5.

For NH Series use approved wire for power
connection from two pole terminal block of
remote blower pack to additional two pole
terminal block inside electrical section of
humidifier.

- 3 -

Depth of trap must be
equal or more than 3” (76 mm)

Remote mounted

Blower pack

Condensate Return

Steam line

Min. 3 ft

(91.4cm)

To Drain

Figure #6

Condensate Return Line Trap

Содержание BLOWER PACKS

Страница 1: ...WER PACKS All Atmospheric Humidifiers Installation Troubleshooting and Exploded Views IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner Form 07 239 1506261 ...

Страница 2: ......

Страница 3: ... WALL MOUNTING 1 REMOTE MOUNTED BLOWER PACKS STEAM LINE 2 CONDENSATE RETURN LINES 3 PRIMARY VOLTAGE CONNECTION 3 PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACK 4 BLOWER PACK CLEARANCES AND DIMENSIONS 5 EXPLODED VIEW OF THE BLOWER PACK 6 7 WIRING DIAGRAM 8 ...

Страница 4: ......

Страница 5: ...ed that balancing valves be used on the steam supply lines to multiple blower packs for equal loading REMOTE MOUNTED BLOWER PACKS WALL MOUNTING 1 Steam and condensate line connections are on the bottom of the blower pack The condensate connection is 3 8 and the steam lines are 7 8 or 1 depending The knock out for the appropriate steam connection must be removed prior to mounting on the wall To rem...

Страница 6: ...s This will also reduce the back pressure and avoid the need to install an extended water trap 5 Ensure that the steam hose does not kink or sag The steam hose becomes more flexible when hot The hose should be supported to prevent water traps Only use steam hose for connection or steam line runs of 5 feet or less See Figure 4 6 To ensure odor free steam always use NORTEC steam hose Check steam hos...

Страница 7: ...ng of condensate return lines Condensate that accumulates in trap will prevent possibility of steam escaping Depth of the trap must be equal or more than 3 76 mm See Figure 6 3 Ensure the trap is 3 minimum under the blower pack and as close to the floor drain as possible PRIMARY VOLTAGE CONNECTION 1 All blower packs for SE and GS unit are wired by others to be powered by an independent circuit 2 A...

Страница 8: ...TAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACK 1 All blower packs are wired by factory if built on and to be powered from the humidifier 2 All built on blower packs are factory wired to the humidifier Primary voltage wiring to the humidifier as described in electrical primary voltage supply wiring is all that is required to power the humidifier and blower packs 4 ...

Страница 9: ...6 91 42 106 48 122 42 106 48 122 Min Front Clearance Inches cm 30 76 30 76 36 91 72 183 84 213 144 366 156 396 144 366 156 396 Remote mounted only Four remote mounted blower packs are recommended on the 200 model Nominal conditions 72 F 35 RH OverheadAnd Frontal Clearances For Blower Packs Note Add 8 70 22 cm to the over all unit height for BOBP for NHTC NHPC Only Blower Pack Weight 120V model 12 ...

Страница 10: ... Packs Installation and Exploded Views 7 22 14 8 3 18 19 2 11 13 15 16 NOTE ITEMS 30 AND 31 NOT SHOWN ITEM 30 CAN REPLACE ITEM 18 AND ITEM 31 CAN REPLACE ITEM 10 IN DIFFERENT WORKING CONFIGURATIONS 9 10 1 20 4 5 6 12 25 17 24 27 28 26 23 21 29 ...

Страница 11: ...ributor plastic Blower Pack 1 13 2522178 Distributor Faceplate Blower Pack 1 14 1475005 Thermostat O Ring 1 15 1073005 Thermostat Control Non Reset 1 16 2524056 Hex Nut 2 56 Steel Zn plated 2 17 2522176 Cabinet Fan Housing Blowerpack 1 18 2522065 Fan Box 115V 110CFM 120x120x38mm 3 19 1504281 Fan cover 4in 6 20 1708808 Hex Nut 10 32 SS 8 21 2524080 Screw Selftapping lin 10 32 Philips Flat Head 24 2...

Страница 12: ...LOWER PACK SPECIFICATION LABEL FOR APPROPRIATE VOLTAGE BLOWER PACK LV TERMINAL BLOCK ON OFF LOOP TO BE WIRED TO HUMIDIFIER WITH OTHER ON OFF CONTROLS IN SERIES S STEP DOWN TRANSFORMER Not required for 115V Model S 0 75A FUSES S S 1 A FUSES Not required for 115V Model 115 VAC BLOWER PACK FAN KIT Orange 550 600V Yellow 440 480V Brown 277V Red 230V Black 208V White Common Transformer Primary Supply C...

Страница 13: ...implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY THE COMPANY s limited warranty on accessories not of AXAIR NORTEC s manufacture such as controls humidistats pumps et...

Страница 14: ......

Страница 15: ...WMH COMPANY www humidity com U S A AxAir NORTEC Inc 826 Proctor Avenue Ogdensburg New York 13669 CANADA AxAir NORTEC Ltd 2740 Fenton Road Ottawa ON K1T 3T7 1 866 NORTEC 1 Fax 613 822 7964 J xl ir Nortec aWMH Company ISO IJ ...

Отзывы: