VS18/VS26
MAINTENANCE & INSTRUCTION BOOKLET
8.5.7 Interbus-S ID and length codes
VS18/VS26 Interbus-S valve islands only offer output connections and each size of Interbus
node is configured to the maximum possible appropriate number of outputs and stores the
corresponding ID code.
Possible VS18/VS26 Interbus-S ID codes:
Number of
stations
Number of
solenoids
ID code
Length code
DIP switch 1
DIP switch 2
4 8 05h
09h
off off
8 16 05h 01h on off
12 24 05h 0Bh
off on
16 32 05h 02h on on
on off
2
1
O
N
Fieldbus PCB
VS2672926-KG00E_05/07 Page