background image

14

•  Read all notes and warnings for the Cooling-mode charging charts prior to using these Heating-mode 

charging charts. Always use safe and environmentally sound methods when handling refrigerant handling 
or servicing the unit. Review the factory literature and safety warnings prior to servicing.

•  When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure 

check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration 
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns 
and weigh in the refrigerant to the amount specified on the unit rating label.

•  Before using 

Table 8

Table 9

, & 

Table 10

, determine the outdoor ambient temperature and the return air temperature 

to the unit. Locate the appropriate location on the units verification chart based on those measurements to determine 
the ideal discharge pressure and temperature. Verify the outdoor fan and compressor are running and the outdoor 
coil is free from frost accumulation. Also verify the system is not operating in defrost mode before inspecting the 
system.

•  Always  use  quality  instruments  that  are  in  good  working  order  to  measure  the  actual  operating  point  of  the 

refrigeration system. The discharge temperature should be within 2 degrees of the ideal value and the pressure 
should be within 2%.

•  The most reliable way of verifying the system is at the correct charge is to evacuate the system and weigh in the 

charge to the amount shown on the rating label. However, if an inspection with these verification charts does not 
line up with the values shown and the ambient temperature is above 50˚ F, then a more accurate way to inspect 
the system for proper charge is with the cooling mode charging charts. Switch the unit into cooling mode and 
allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mode charts and 
procedures.

Before changing the unit charge, always inspect the following items first:
1. Inspect the liquid line temperature on the inlet and outlet of the filter dryers. If it is the factory dryer and in good 

condition there should be no temperature difference. If the temperature difference is larger than 5˚, replace the filter 
dryer with one that is bi-directional and has acid removal capability. Refer to the unit RPL for the recommended 
part number and size.

2. Inspect the units input voltage. Units operating at less than 95% of the nominal voltage may deviate more from the 

chart then previously stated.

3. Inspect the input voltage for a phase imbalance. Units with greater then a 2% disparity will not operate at the rated 

performance.

4. Verify that the unit filters are installed and are clean. The pressure drop across the filters should not exceed 0.08 

in-W.C.

5. Inspect the indoor coil, indoor blower and blower motor for cleanliness, clogging, and proper operation.
6. Inspect the system for leaks. If any leaks are detected, repair them immediately. Re-inspect the return air and 

ambient temperatures and verify that the correct system point on the verification chart was selected.

DO NOT use the charts in systems that have the fan cycling under a low-ambient control. Low-ambient controls are 
for cooling operation. In heating mode, the low ambient control should be disabled. Unless the unit is in defrost mode, 
the outdoor fan should always operate in conjunction with the compressor.

IMPORTANT NOTE: If the unit is equipped with a liquid valve with an outdoor restrictor (Figure 2 page 4), 
then it is not possible to measure the liquid pressure. To approximate the liquid pressure, subtract 7 psig 
from the discharge pressure.

Heat Mode Tables & Application Notes - (Heating Only)

 Shaded boxes indicate flooded conditions.

 Rated design values. The suction pressure will be lower than design value if indoor air flow, entering dry 

bulb, or entering wet bulb temperatures are lower than design.

1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. Discharge temperatures less than charted values indicate an overcharged system.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode 

at ambient above 70°F.

Содержание T4BD-042 Series

Страница 1: ...n how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well...

Страница 2: ...orotherhazardous conditions which may result in personal injury or property damage Installation of equipment may require brazing operations Installer must comply with safety codes andwearappropriatesa...

Страница 3: ...iled immediately with the carrier Pleaseconsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat P...

Страница 4: ...dryer is provided with the unit and must be installedintheliquidlineofthesystem Iftheinstallation replaces a system with a filter dryer already present in the liquid line the filter dryer must be rep...

Страница 5: ...y andtherestrictororifice whilebeingcarefulnottoscratch either part Carefully remove the restrictor orifice from the valve body See Figure 3 page 4 3 Check the actual size of the new orifice NOTE The...

Страница 6: ...Diagnostics Module Select Models Only The CoreSenseTM Diagnostics Module Figure 5 page 7 is a breakthrough innovation for troubleshooting heatpumpandairconditioningsystemfailures Themodule installs ea...

Страница 7: ...tart Check List Verify the unit is level and has sufficient clearances for unobstructed airflow Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment acce...

Страница 8: ...2 sec and does not start within 35 sec 10x consecutive Red Flash4 Yellow Off Code5 Yellow Flash 5 Compressor moderate run trip Compressor runs for 15 min to 18 hrs followed by a compressor trip lastin...

Страница 9: ...Data sheet for additional charging information Outdoor units with non AHRI listed indoor coils are not recommended and deviations from rated airflows or non listedcombinationsmayrequiremodificationtot...

Страница 10: ...ange of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit efficiency EER or rated...

Страница 11: ...below the curve T4BD 048KA Charging Chart Cooling Figure 7 Charging Chart for 4 Ton Units TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95...

Страница 12: ...ring wet bulb temperatures are lower than design 1 All pressures are listed in psig and all temperatures in F 2 Discharge temperatures greater than charted values indicate an undercharged system 3 Dis...

Страница 13: ...LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 121 244 135 123 245 135 267 141 125 246 135 268 141 290 147 127 247 136 269 142 291 147 313 154 129 248 136 270 142 292 148 314 154 336 160 131 271 142 293 148 31...

Страница 14: ...the liquid line temperature on the inlet and outlet of the filter dryers If it is the factory dryer and in good condition there should be no temperature difference If the temperature difference is lar...

Страница 15: ...0 221 232 105 45 239 250 112 60 257 268 120 75 275 286 127 90 288 299 136 105 314 325 146 121 339 350 155 31 228 239 103 46 245 256 110 61 261 272 118 76 278 289 125 91 295 306 133 106 321 332 141 122...

Страница 16: ...ot suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 4...

Страница 17: ...0 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air h...

Страница 18: ...ts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handle...

Страница 19: ...19...

Страница 20: ...NO INSTALLER NAME CITY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO 7096...

Отзывы: