10
Charging Charts & Application Notes - (Cooling Only)
• This equipment’s cooling system contains refrigerant under high pressure. Always use safe and
environmentally sound methods when handling refrigerant handling or servicing the unit. Review the
factory literature and safety warnings prior to servicing.
• When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns
and weigh in the refrigerant to the amount specified on the unit rating label.
• The charging charts below (
, &
are valid for a variety of indoor, return air conditions and
are most influenced by the outdoor ambient temperature, outdoor fan operation and the unit operating voltage.
Before using these charts, make sure the unit is in a stable operating mode. As shown in the charts, the ideal
system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of
sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency
(EER) or rated Coefficient of Performance (COP) in heating mode.
• To inspect a systems operation using quality instruments, match the measured liquid temperature to the units
chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.
• For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase
balance and the refrigeration system for leaks.
• Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more
significant deviation than the amount stated above.
•
DO NOT use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient
kit instructions for more information. (If applicable)
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75
80
85
90
95
100
105
110
115
120
125
130
135
Liquid Temperature (
0
F)
Liquid Pressure
(psig)
Remove refrigerant when above the curve
Add refrigerant when below the curve
T4BD-042KA Charging Chart - Cooling
Figure 6.
Charging Chart for 3.5 Ton Units (TXV Matches)