*SK - DOWNFLOW FURNACES - 80+ AFUE

Model Number

&

Heating Input

(Btuh)

Motor

Speed

External Static Pressure (Inches Water Column)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

SK054C-23A

(54,000)

High*

1,375

29

1,340

30

1,300

31

1,270

31

1,225

33

1,175

34

1,115

36

1,035

39

Med-High

1,155

35

1,130

35

1,110

36

1,085

37

1,055

38

1,015

39

975

41

910

44

Med-Low**

790

51

775

52

765

52

750

53

730

55

700

57

665

60

610

66

Low

650

62

640

63

630

63

610

66

590

68

565

71

530

75

480

83

SK072C-24B

(72,000)

High*

1,610

33

1,590

34

1,575

34

1,560

34

1,540

35

1,495

36

1,460

37

1,415

38

Med-High

1,295

41

1,275

42

1,260

42

1,250

43

1,220

44

1,195

45

1,170

46

1,120

48

Med-Low**

1,155

46

1,135

47

1,115

48

1,095

49

1,065

50

1,040

51

1,015

53

980

54

Low

910

59

885

60

860

62

835

64

810

66

785

68

765

70

735

73

SK090C-24B

(90,000)

High*

1,675

40

1,655

40

1,640

41

1,620

41

1,590

42

1,560

43

1,520

44

1,475

45

Med-High

1,330

50

1,315

51

1,300

51

1,280

52

1,255

53

1,230

54

1,200

56

1,150

58

Med-Low**

1,180

56

1,165

57

1,150

58

1,135

59

1,115

60

1,090

61

1,060

63

1,010

66

Low

940

71

925

72

900

74

880

76

850

78

825

81

795

84

760

88

SK108C-35C

(108,000)

High*

2,395

33

2,335

34

2,285

35

2,230

36

2,200

36

2,140

37

2,080

38

2,000

40

Med-High

2,190

37

2,135

37

2,115

38

2,080

38

2,030

39

1,975

41

1,915

42

1,810

44

Med-Low**

1,785

45

1,770

45

1,740

46

1,725

46

1,685

47

1,645

49

1,615

50

1,565

51

Low

1,145

70

1,110

72

1,070

75

1,035

77

1,000

80

950

84

905

88

835

96

SK126C-45D

(126,000)

High*

2,445

38

2,395

39

2,385

39

2,330

40

2,275

41

2,225

42

2,130

44

2,015

46

Med-High

2,195

43

2,170

43

2,140

44

2,120

44

2,090

45

2,030

46

1,975

47

1,855

50

Med-Low**

1,795

52

1,780

52

1,770

53

1,760

53

1,725

54

1,690

55

1,655

56

1,610

58

Low

1,480

63

1,475

63

1,450

64

1,440

65

1,440

65

1,415

66

1,405

66

1,375

68

NOTES:

* Factory Set Cooling Speed

** Factory Set Heating Speed

1. Temperature rises in the table are approximate. Actual temperature rises may vary.

2. Temperature rises shaded gray are for reference only. These conditions are not recommended.

Table 5. Maximum Airfl ow & Temperature Rises (° F) - Downfl ow Furnaces

Содержание *SA Upfl ow / Horizontal

Страница 1: ...upplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des bless...

Страница 2: ...r Connections 11 Upflow Horizontal Furnaces 11 Side Return Installations 11 Bottom Return Installations 12 Downflow Furnaces 12 Acoustical Treatments 12 FURNACE INSTALLATION 12 General Requirements 12...

Страница 3: ...ry or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code NFPA54 ANSI Z223 1 or the Na...

Страница 4: ...ermostat The installation must include a properly installed filter in the return air system with no by pass air The filter must be inspected frequently and replaced when necessary Combustion air must...

Страница 5: ...opane Installation Codes NSCNGPIC Venting Systems and Air Supply for Appliances Duct Systems US and CANADA Air Conditioning Contractors Association ACCA Manual D Sheet Metal and Air Conditioning Contr...

Страница 6: ...n vacuent correctement tel que prescrit ci dessus rouvrir les portes et les fen tres et remettre les ventilateurs d vacuation les registres de foyers et tout autre appareil fonctionnant au gaz leur ta...

Страница 7: ...air from that space Furnaceclosets smallequipmentroomsandgaragesare confined spaces Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from...

Страница 8: ...or Wall 12 Max 12 Max Furnace NOTE Each opening to outside must be at least 1 sq in per 4 000 Btuh of total input rating Vent or Chimney Water Heater See Note Total Input Rating Btuh Minimum Free Area...

Страница 9: ...ve pressure draft and must be vented vertically or near vertical Additionally it is important to guard against excessive condensation WARNING Upon completion of the furnace installation carefully insp...

Страница 10: ...xisting vent system should also be checked to make sure it remains in compliance with NFGC If it isn t the vent system must be brought into compliance before installing the furnace Horizontal Venting...

Страница 11: ...e furnace is equal to the return air supply under normal indoor return air applications When a cooling system is installed which uses the furnace blower to provide airflow over the indoor coil the coi...

Страница 12: ...ur knockouts to expose the blower assembly Position the return air duct over the opening in the side and secure together with sheet metal screws The screws must penetrate the duct and furnace casing W...

Страница 13: ...hers Securethesupportframetothe rafters with lag bolts The furnace can also be suspended using steel straps around each end of the furnace The straps should be attached to the furnace with sheet metal...

Страница 14: ...e the furnace in reverse order Bottom Panel Removal The steps listed below describe how to remove the bottom panel from the furnace See Figure 11 1 Remove the door 1 from the blower compartment 2 Disc...

Страница 15: ...IPING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be performed by a qualified installer service a...

Страница 16: ...2 000 feet the input needs to be reduced 8 at 3 000 feet 12 etc This deration is in reference to the input rate and gas heating value at sea level Toderatethefurnacerequiresknowingtheheatingvalueof t...

Страница 17: ...TATUS FLAME 180 COOL HEAT 120 90 60 BLOWER OFF DELAY LOW ML MH HIGH EAC L1 XFMR HUM 24V L1A 5 NEUTRALS 2 6 3 4 1 7 8 9 5 2 6 3 4 1 FAN 8 3 5 See Note R C Y G W STATUS FLAME 180 COOL HEAT 120 90 60 BLO...

Страница 18: ...erty damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing...

Страница 19: ...is connected Furnace Model SA SK Furnace Input Btuh Cabinet Width in Nominal Electrical Supply Maximum Operating Voltage Minimum Operating Voltage Maximum Furnace Amperes Minimum Wire Gauge Maximum F...

Страница 20: ...municate to a fixed speed or variable speed high efficiency motor that may be optionally installed Please contact your distributor for the proper upgrade motor kit Heat Anticipator Set the heat antici...

Страница 21: ...cal power to the furnace 3 FollowtheOperatingInstructionsonthelabelattached to the furnace 4 Setthethermostataboveroomtemperatureandverify the Operating Sequence Page 22 5 After 5 minutes of operation...

Страница 22: ...t switch should turn off the gas valve when the return is blocked time depends on how well the return air is blocked The circulating air and combustion blowers should continue to run when the limit sw...

Страница 23: ...will close the gas valve and initiate the shutdown cycle GasValve Controls the flow of gas to the burners When the gas valve is energized it automatically opens and regulates the gas pressure in the...

Страница 24: ...urnace 4 Turn the gas control switch to the OFF position 5 Disconnect the wires from the gas valve igniter flame sensor and flame rollout switch CAUTION To prevent damage to the unit or internal compo...

Страница 25: ...ays however the flue vent system and burners should be inspected and cleaned if required by a qualified service technician annually to ensure continued safe operation Pay attention to any deterioratio...

Страница 26: ...23A 072C 24B 17 1 2 11 3 4 15 7 8 16 1 8 090C 24B 072C 35C 21 14 19 3 8 19 7 8 090C 35C 108C 35C 126C 45D 24 1 2 15 1 4 22 7 8 23 1 8 NOTE Dimensions shown in Inches 18 5 8 C 7 34 1 2 22 1 2 28 25 3 8...

Страница 27: ...685 32 1 645 32 1 590 34 1 550 34 1 485 36 1 415 38 Med High 1 400 38 1 360 39 1 340 40 1 310 41 1 275 42 1 245 43 1 190 45 1 125 47 Med Low 1 235 43 1 215 44 1 180 45 1 155 46 1 130 47 1 100 48 1 060...

Страница 28: ...63 1 225 65 1 175 68 SA108C 35C Side Return 108 000 High 2 295 35 2 235 36 2 180 37 2 110 38 2 050 39 1 975 41 1 900 42 1 810 44 Med High 2 130 38 2 075 39 2 035 39 1 970 41 1 915 42 1 845 43 1 765 4...

Страница 29: ...51 1 300 51 1 280 52 1 255 53 1 230 54 1 200 56 1 150 58 Med Low 1 180 56 1 165 57 1 150 58 1 135 59 1 115 60 1 090 61 1 060 63 1 010 66 Low 940 71 925 72 900 74 880 76 850 78 825 81 795 84 760 88 SK...

Страница 30: ...n Yellow LED Continuous Flash On Alternating Flash IGNITOR INDUCER FLAME SENSOR C BLOWER LIMIT SWITCH DOOR SWITCH R 4 SPEED MOTOR WHITE RED BLUE ORANGE BLACK BLOWER LIMIT SWITCH GAS VALVE H MH ML L C...

Страница 31: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 32: ...57 57 ORIFICE SIZE 9 0 9 0 9 0 9 0 9 0 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 59 57 57 57 57 57 ORIFICE SIZE 8 5 8 5 8 5 8 5 8 5 8 5 MANIFOLD PRESSURE LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE...

Страница 33: ...LD PRESSURE 9 000 to 9 999 FT 51 49 49 49 49 49 ORIFICE SIZE 2 6 2 8 2 8 2 8 2 8 2 8 MANIFOLD PRESSURE Table 11 High Altitude Deration Chart for Natural Gas Low Heating Value NATURAL GAS with LOW HEAT...

Страница 34: ...oll Out Switch Transformer Blower Assembly Control Board Main Air Limit Switch Figure 20 Furnace Components Combustion Tube Gas Manifold Gas Valve Inducer Assembly Control Board Pressure Switch Transf...

Страница 35: ...35...

Страница 36: ...tion of this appliance Some local codes require licensed installation service personnel for this type of equipment Please read all instructions carefully before starting the installation Return these...

Отзывы: