Figure 4. Wiring diagram for 1.5 - 4 ton models (without coreSense
tm
)
Single Phase
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
710388B
(Replaces 710388A)
0109
WIRING DIAGRAM
Split System Air Conditioner (Outdoor Section)
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 deg C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Anti-Short Cycle Timer (ASCT) may or may not be installed in the unit. If desired,
ASCT is factory installed on select models only or may be field installed as shown using
manufacturer’s approved kit. If not present, connect Yellow and Black wires per Note 6.
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
¢710388B¤
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
208/230V
CC
ASCT
ASCT
(SEE NOTE 7)
H
C
F
CCH
(OPTIONAL)
R
C
S
S
C
R
L2
T2
COMPRESSOR
CONTACTS
L1
T1
COMPRESSOR
OUTDOOR FAN
MOTOR
24 VOLT FIELD
CONNECTIONS
HPS
HPS
T2
T1
T3
ASCT
(SEE
NOTE 7)
GROUNDING
SCREW
L1 L2 GND
T1
T2
L1
L2
OUTDOOR
FAN MOTOR
C
S
DUAL
CAPACITOR
R
3
1
2
START
CAPAC
START
RELAY
BLACK
BLUE
ORANGE
YELLOW
CONTACTOR
YELLOW
BLACK
RED
CRANKCASE
HEATER
(OPTIONAL)
YELLOW BLACK
SEE NOTE 6
RED OR
YELLOW
BLACK
RED OR
RED BLACK
BLACK OR
BLK WHT
C
S
R
YELLOW
OR
YELLOW
BLACK
RED OR
RED BLACK
H
C
F
electrical inFormation
table 10. led diagnostics for coreSense
tm
diagnostics module
alert code
alert condition
locK leVel
locK indication
normal run
Solid Yellow
Normal operation, no trip
N/A
N/A
code 1
Yellow Flash 1
Long run time. Compressor is on running for more than 18 hours.
(Code1 is disabled in Heat Pump Mode)
N/A
N/A
code 2
Yellow Flash 2
Compressor (pressure) trip. Compressor runs for 12 sec to 15 min
followed by a compressor trip condition lasting for more than 7 min.
4x consecutive
Red: Flash2
Yellow: Off
code 3
Yellow Flash 3
Pressure switch cycling. Compressor runs for 12 sec to 15 min followed
by a compressor trip lasting between 35 sec to 7 min.
4x consecutive
or 10x total
Red: Flash3
Yellow: Off
code 4
Yellow Flash 4
Locked rotor. Compressor trips within a compressor run time of 12 sec
and does not start within 35 sec.
10x consecutive
Red: Flash4
Yellow: Off
code 5
Yellow Flash 5
Compressor (moderate run) trip. Compressor runs for 15 min to 18 hrs
followed by a compressor trip lasting longer than 7 min.
4x consecutive
or 10x total
Red: Flash5
Yellow: Off
code 9
Red Flash 9
The current to the PROT terminal is greater than 2A.
Current >2A
for 40ms
Red: Flash9
Yellow: Off
trip
Solid Red
Demand is present, but compressor is not running.
N/A
N/A