background image

2

important SaFety inFormation

INSTALLER: 

Please read all instructions before servicing 

this equipment. Pay attention to all safety warnings and any 

other special notes highlighted in the manual. Safety markings 

are used frequently throughout this manual to designate a 

degree or level of seriousness and should not be ignored.

Warning

 

indicates a potentially hazardous situation that 

if not avoided, could result in personal injury or death.

caUtion

 

indicates a potentially hazardous situation that 

if not avoided, may result in minor or moderate injury or 

property damage.

 Warning:

Shut off all electrical power to the unit before 

performing any maintenance or service on the 

system. Failure to comply may result in personal 

injury or death.

 Warning:

Unless noted otherwise in these instructions, only 

factory authorized parts or accessory kits may 

be used with this product. improper installation, 

service, adjustment, or maintenance may cause 

explosion, fire, electrical shock or other hazardous 

conditions which may result in personal injury 

or property damage

 Warning:

S4Be split system air conditioners are shipped 

charged with r410a refrigerant and ready 

for installation. if repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. Under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

 Warning:

the information listed in this manual must be 

followed during the installation, service, and 

operation of this unit. Unqualified individuals 

should not attempt to interpret these instructions 

or install this equipment. Failure to follow safety 

recommendations could result in possible 

damage to the equipment, serious personal 

injury or death.

 caUtion:

this unit uses refrigerant r-410a. do not use 

any other refrigerant in this unit. Use of another 

refrigerant will damage the unit.

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this type of 

equipment. Local codes and regulations take precedence 

over any recommendations contained in these instructions. 

Consult local building codes and the National Electrical 

Code (ANSI CI) for special installation requirements.

•  All electrical wiring must be completed in accordance with 

local, state and national codes and regulations and with 

the National Electric Code (ANSI/NFPA 70) or in Canada 

the Canadian Electric Code Part 1 CSA C.22.1.

•  This equipment contains liquid and gaseous refrigerant 

under high pressure. DO NOT USE ANY PORTION OF THE 

CHARGE FOR PURGING OR LEAK TESTING.Installation 

or servicing should only be performed by qualified trained 

personnel thoroughly familiar with this type equipment.

•  Fully annealed, refrigerant grade copper tubing should be 

used when installing the system. Refrigerant suction line 

tubing should be fully insulated.

•  Installation of equipment may require brazing operations. 

Installer must comply with safety codes and wear 

appropriate safety equipment (safety glasses, work gloves, 

fire extinguisher, etc.) when performing brazing operations.

•  Follow all precautions in the literature, on tags, and on 

labels provided with the equipment. Read and thoroughly 

understand the instructions provided with the equipment 

prior to performing the installation and operational checkout 

of the equipment.

•  Refrigerant and electrical line should be routed through 

suitably waterproofed openings to prevent water from 

leaking into the structure.

Содержание S4BE-018KA Series

Страница 1: ...ant SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connecting Refrigerant Tubing Between the Indoor Outdoor Unit 3 ELECTRICAL WIRING 4 Pre Electrical Checklist 4 Line Voltage 4 Grounding 5 CoreSenseTM Diagnostics Module 5 Compressor Protection 5 Resetting Alert C...

Страница 2: ...ttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal injury or death CAUTION This unit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit The installer must comply with all local codes and regulations which govern the insta...

Страница 3: ...e the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overheadobstructions Figure1 poorlyventilatedareas and areas subject to accumulation of debris should be avoided Consideration should be given to availability of electric...

Страница 4: ...r of bends in the tubing If precise forming of refrigerant lines is required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of foreign debris during installation Every effort should be made by the ...

Страница 5: ...noraminielectronics screwdriver This button must be pressed and held for a minimum of one second for the module to be reset Pressing theresetbuttonclearstheimmediatelockcodeandtheseven day operating history It will not clear the permanent module history In the case of the three wire module the codes can be reset or cleared by cycling power to the module This can be done by disengaging the Common C...

Страница 6: ...ep 1 is greater than the required liquid refrigerant pressure determined in Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 t...

Страница 7: ...rging Table for 1 5 Ton Models Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design value if indoor air flow entering dry bulb or entering wet bulb temperatures are lower than design 1 All pressures are listed in psig and all temperatures in F 2 Discharge temperatures greater than charted values indicate an undercharged system 3 In Cooling Mode su...

Страница 8: ...ss Dis Temp 128 244 121 130 245 124 267 125 132 245 128 268 128 290 128 134 246 132 269 132 291 132 313 132 136 247 136 269 136 292 135 314 136 337 136 138 270 139 293 139 315 139 337 139 360 139 140 293 143 316 142 338 142 360 142 383 143 142 317 146 339 146 361 146 384 146 406 146 144 317 149 340 149 362 149 384 149 407 149 146 341 152 363 152 385 152 407 152 148 364 155 386 155 408 155 150 387 ...

Страница 9: ...ress Dis Temp 129 232 124 131 233 127 255 125 133 233 131 255 129 278 127 135 234 135 256 132 278 131 300 129 137 234 140 257 136 279 134 301 132 323 131 139 257 141 279 138 302 135 324 134 346 132 141 280 142 302 139 324 137 347 135 369 134 143 303 143 325 140 347 139 369 137 392 135 145 303 146 326 144 348 142 370 140 392 138 147 326 147 348 145 371 143 393 142 149 349 148 371 146 393 144 151 37...

Страница 10: ...ess Dis Temp 122 243 133 124 244 136 267 136 126 245 140 268 140 291 139 128 246 143 269 143 292 143 315 143 130 247 147 270 147 293 146 315 146 338 146 132 270 150 293 150 316 150 339 150 362 150 134 294 153 317 153 340 153 363 153 386 153 136 318 156 341 156 364 157 387 157 410 157 138 319 160 341 160 364 160 387 160 410 160 140 342 163 365 163 388 163 411 163 142 366 166 389 166 412 166 144 390...

Страница 11: ...intenance on this equipment requires certain mechanical skills and tools If you do not possess these skills contact your dealer for maintenance Consult your local dealer about the availability of maintenance contracts Routine maintenance should include the following Inspect and clean or replace air filters at the beginning of each heating and cooling season or more frequently if required Inspect t...

Страница 12: ... GND T1 T2 L1 L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED OR RED BLACK BLACK OR BLK WHT C S R YELLOW OR YELLOW BLACK RED OR RED BLACK H C F Electrical Information Table 10 LED Diagnostics for CoreSenseTM Diagnostics Module ALERT CODE ALERT CONDIT...

Страница 13: ...ecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremely long run cycle disabled in HP mode Status LED Description Lockout Level Lockout Indication Comprsesor Pressure Trip Disch or suct pressure out of limits or compressor overloaded Short Cycling Compresso...

Страница 14: ...see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 1 Couper le courant avant de faire letretien 2 Empl...

Страница 15: ...oderate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLACK GRAY RED 208 230V H C R C S CC Iput2 C ECM L2 L1 Iput1 CC Contactor Coil LPS Low Pressure Switch HPS High Pressure Switch HPS CORESENSE MODULE P C C Y Y 24 VOLT FIELD CONNECTIONS 208 230V Split S...

Страница 16: ...__________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIGERATION SYSTEM Was unit given 24 hr warm up period for crankcase heaters YES NO Stage 1 Liquid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ P...

Отзывы: