background image

5

grounding

 Warning:

the unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the National 

Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical 

Code. Use the grounding lug provided in the control box for 

grounding the unit.

coreSense

tm

 diagnostics module

(Select models only)

The CoreSense

TM

 Diagnostics Module (

Figure 2

) is a 

breakthrough innovation for troubleshooting heat pump and 

air conditioning system failures. The module installs easily 

in the electrical box of the outdoor unit near the compressor 

contactor.By using the compressor as a sensor, CoreSense 

Diagnostics helps the service technician more accurately 

troubleshoot system and compressor fault conditions.
A flashing LED indicator communicates the ALERT code 

and a diagnostic key is also imprinted on the side of the 

module to quickly direct the technician to the root cause of 
a problem.

 

Alert identification codes are also listed in 

Table 

10, (page 12)

.

Compressor Protection

The CoreSense

TM

 Diagnostics module utilizes proprietary 

algorithms to protect the compressor and system from 

repeated trips of system pressure controls and the compressor 

internal overload. The protection terminal of the module should 

be wired in series with the system low pressure and high 

pressure cutouts, as well as the compressor contactor. When 

the module detects a series of trips as described below, it 

will activate a lockout feature that opens the normally closed 

protection contacts in the module, thereby cutting power to 

the contactor and shutting off the compressor.

Resetting Alert Codes

When the CoreSense

TM

 Diagnostics module has detected a 

series of adverse conditions that have caused it to lockout 

the compressor, and after the issue has been resolved, it 

is necessary to manually reset the module in order to clear 

the present alert code.
The primary way of clearing the code and resetting the alert 

is to press the reset button located on the module.

note:

 Pressing the reset will require a pin or a mini electronics 

screwdriver. This button must be pressed and held for a 

minimum of one second for the module to be reset. Pressing 

the reset button clears the immediate lock code and the seven 

day operating history. It will not clear the permanent module 

history. In the case of the three-wire module, the codes can 

be reset or cleared by cycling power to the module. This can 

be done by disengaging the Common (C) terminal. This will 

not clear the seven day operating history.

Figure 2. coreSense

tm

 diagnostics module

Compressor
Common Wire

Reset Button

Trip / Lock
(Red LED)

Run / Alert
(Yellow LED)

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and the 

indoor equipment.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must comply 

with the current provisions of the NEC (ANSI/NFPA 70) 

and with applicable local codes having jurisdiction.

•  The  low  voltage  wires  must  be  properly  connected  to 

the units low voltage terminal block. Recommended wire 

gauge and wire lengths for typical thermostat connections 
are listed in 

Table 2

.

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on 

an outside wall or any other location where its operation 

may be adversely affected by radiant heat from fireplaces, 

sunlight, or lighting fixtures, and convective heat from 

warm air registers or electrical appliances. Refer to the 

thermostat manufacturer’s instruction sheet for detailed 

mounting and installation information.

Start Up & adJUStmentS

pre-Start check list

  Verify the indoor unit is level and allows proper condensate 

drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/control 

panels are in place.

  Verify air filters are cleaned and properly installed.

  Verify duct work is sealed to prevent air leakage.

 Verify line voltage power leads are securely connected 

and the unit is properly grounded.

  Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

  Verify the thermostat is wired correctly.

table 2. thermostat Wire gauge

thermoStat

Wire gaUge

maximUm recommended

 thermoStat Wire length (Ft)

24

25

22

45

20

70

18

110

Содержание S4BE-018KA Series

Страница 1: ...ant SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connecting Refrigerant Tubing Between the Indoor Outdoor Unit 3 ELECTRICAL WIRING 4 Pre Electrical Checklist 4 Line Voltage 4 Grounding 5 CoreSenseTM Diagnostics Module 5 Compressor Protection 5 Resetting Alert C...

Страница 2: ...ttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal injury or death CAUTION This unit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit The installer must comply with all local codes and regulations which govern the insta...

Страница 3: ...e the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overheadobstructions Figure1 poorlyventilatedareas and areas subject to accumulation of debris should be avoided Consideration should be given to availability of electric...

Страница 4: ...r of bends in the tubing If precise forming of refrigerant lines is required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of foreign debris during installation Every effort should be made by the ...

Страница 5: ...noraminielectronics screwdriver This button must be pressed and held for a minimum of one second for the module to be reset Pressing theresetbuttonclearstheimmediatelockcodeandtheseven day operating history It will not clear the permanent module history In the case of the three wire module the codes can be reset or cleared by cycling power to the module This can be done by disengaging the Common C...

Страница 6: ...ep 1 is greater than the required liquid refrigerant pressure determined in Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 t...

Страница 7: ...rging Table for 1 5 Ton Models Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design value if indoor air flow entering dry bulb or entering wet bulb temperatures are lower than design 1 All pressures are listed in psig and all temperatures in F 2 Discharge temperatures greater than charted values indicate an undercharged system 3 In Cooling Mode su...

Страница 8: ...ss Dis Temp 128 244 121 130 245 124 267 125 132 245 128 268 128 290 128 134 246 132 269 132 291 132 313 132 136 247 136 269 136 292 135 314 136 337 136 138 270 139 293 139 315 139 337 139 360 139 140 293 143 316 142 338 142 360 142 383 143 142 317 146 339 146 361 146 384 146 406 146 144 317 149 340 149 362 149 384 149 407 149 146 341 152 363 152 385 152 407 152 148 364 155 386 155 408 155 150 387 ...

Страница 9: ...ress Dis Temp 129 232 124 131 233 127 255 125 133 233 131 255 129 278 127 135 234 135 256 132 278 131 300 129 137 234 140 257 136 279 134 301 132 323 131 139 257 141 279 138 302 135 324 134 346 132 141 280 142 302 139 324 137 347 135 369 134 143 303 143 325 140 347 139 369 137 392 135 145 303 146 326 144 348 142 370 140 392 138 147 326 147 348 145 371 143 393 142 149 349 148 371 146 393 144 151 37...

Страница 10: ...ess Dis Temp 122 243 133 124 244 136 267 136 126 245 140 268 140 291 139 128 246 143 269 143 292 143 315 143 130 247 147 270 147 293 146 315 146 338 146 132 270 150 293 150 316 150 339 150 362 150 134 294 153 317 153 340 153 363 153 386 153 136 318 156 341 156 364 157 387 157 410 157 138 319 160 341 160 364 160 387 160 410 160 140 342 163 365 163 388 163 411 163 142 366 166 389 166 412 166 144 390...

Страница 11: ...intenance on this equipment requires certain mechanical skills and tools If you do not possess these skills contact your dealer for maintenance Consult your local dealer about the availability of maintenance contracts Routine maintenance should include the following Inspect and clean or replace air filters at the beginning of each heating and cooling season or more frequently if required Inspect t...

Страница 12: ... GND T1 T2 L1 L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED OR RED BLACK BLACK OR BLK WHT C S R YELLOW OR YELLOW BLACK RED OR RED BLACK H C F Electrical Information Table 10 LED Diagnostics for CoreSenseTM Diagnostics Module ALERT CODE ALERT CONDIT...

Страница 13: ...ecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremely long run cycle disabled in HP mode Status LED Description Lockout Level Lockout Indication Comprsesor Pressure Trip Disch or suct pressure out of limits or compressor overloaded Short Cycling Compresso...

Страница 14: ...see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 1 Couper le courant avant de faire letretien 2 Empl...

Страница 15: ...oderate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLACK GRAY RED 208 230V H C R C S CC Iput2 C ECM L2 L1 Iput1 CC Contactor Coil LPS Low Pressure Switch HPS High Pressure Switch HPS CORESENSE MODULE P C C Y Y 24 VOLT FIELD CONNECTIONS 208 230V Split S...

Страница 16: ...__________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIGERATION SYSTEM Was unit given 24 hr warm up period for crankcase heaters YES NO Stage 1 Liquid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ P...

Отзывы: