background image

11

temperature selector below the existing room 
temperature. Allow the cooling system to operate 
for several minutes and check for the discharge 
of cool air at the supply registers.

Short Cycle Protection
The control circuit is equipped with a time-delay 
feature for protection against short cycling. 
With the system operating in the cooling mode, 
gradually raise the thermostat temperature setting 
until the whole system de-energizes. Immediately 
lower the thermostat temperature to the original 
setting and verify that the indoor blower is 
energized. After approximately 5 minutes the 
compressor and the outdoor fan will energize.

Emergency Heat
(Available only when Electric heat is supplied) 
Set the thermostat’s system mode to EM HT and 
the fan mode to either AUTO (intermittent air) or 
to ON (continuous air). Change the thermostat’s 
temperature selector above the existing room 
temperature and check the following:
1. The thermostat auxiliary heat light (RED) 

should be on.

2.  The heat pump compressor and the fan should 

not run; low voltage circuit remains energized.

3. The blower will run according to the 

thermostat’s fan mode setting.

Defrost Test  Procedure

1. Terminals 

R

 & 

C

 must have 18 - 30V between 

them for defrost sequences to initiate.

2  With thermostat in heat mode (

Y

 connected to 

R

), short (and hold) the TEST pins together. 

NOTE: 

This energizes the reversing valve to 

initiate a forced defrost, bypass the ASCD, and 
allow the high stage compressor to turn on 
immediately (if the REMOVE FOR NO DELAY 
jumper at 

P6

 is removed). If the jumper at 

P6

 

is installed, the compressor will energize after 
a 30 second delay.

3. Remove the short on the TEST pins.
•  If the Coil temperature is above the Terminate 

Temperature setting, the defrost cycle will 
terminate (reversing valve de-energizes).

•  If the coil temperature is below the Terminate 

Temperature setting, the defrost cycle will 
continue for 14 minutes (or until the coil 
temperature rises above the Terminate 
Temperature setting). Short the TEST pins 
for 1 second or more to force the control 
out of defrost and back to heating mode 
(reversing valve de-energized). Compressor 
will start immediately (if the REMOVE 
FOR NO DELAY jumper is removed). 

NOTE: 

If the jumper is installed, the compressor 

will energize after a 30 second delay.

Anti Short Cycle Timer Test

The 5 minute time delay feature can be bypassed 
by shorting the TEST pins together.

Heating Mode
When the TEST pins are shorted together for 
more than 1 second, the control will switch 
between defrost mode and heating mode.

Cooling Mode
When the TEST pins are shorted together for 
more than 1 second, the Anti Short Cycle Timer 
will be bypassed.

Adjustment of Refrigerant Charge

 CAUTION:

The Q5RD heat pump contains 
liquid and gaseous refrigerant 
under pressure. Adjustment of 
refrigerant charge should only 
be attempted by qualifi ed, trained 
personnel thoroughly familiar with 
the equipment and safe responsible 
refrigerant handling procedures. 
Under no circumstances should 
the homeowner attempt to install 
and/or service this equipment. 
Failure to comply with this warning 
could result in equipment damage, 
personal injury, or death.

•  The unit must be charged while both fi rst and 

second stages are operating.

•  To achieve rated capacity and effi ciency the 

compressor must be exposed to refrigerant 
for at least 24 hours prior to running and then 
must be run for a minimum of 12 hours. See 
refrigerant charging charts for cooling mode 
operation (Tables 5 - 10, pages 14 - 16).

Charging an R-410A Unit in AC Mode with 
Outdoor Temperatures Above 65° F

1.  With the system operating at steady-state, 

measure the liquid refrigerant pressure in 
psig at the service valve.

2.  Measure the liquid refrigerant temperature 

(° F) at the service valve.

3.   For the temperature measured, determine the 

required liquid refrigerant pressure from the 
appropriate charging charts.

•  If the pressure measured in step 1 is greater 

than the required liquid refrigerant pressure 
determined in step 4, then there is too much 
charge in the system. Remove refrigerant and 
repeat steps 1 through 3 until the system is 

Содержание Q5RD Series

Страница 1: ...check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified i...

Страница 2: ...Low Pressure Switch 13 High Pressure Switch 13 Unit Maintenance 13 Figures Tables 13 Figure 9 Unit Dimensions 13 Table 4 Q5RD Physical Data 13 Charging Tables Cooling Mode 14 Table 5 Q5RD X24K 2 Ton U...

Страница 3: ...f the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit will develop a coating of snow and ice on the heat transfer coil Thi...

Страница 4: ...tdoor coil must be maintained in order to achieve rated performance See Figure 2 page 5 for minimum clearances to obstructions Consideration should also be given to availability of electric power serv...

Страница 5: ...ngto NationalFireProtectionAssociation Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of Ame...

Страница 6: ...tion from under the home by cuttingasmallholeinthesub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located...

Страница 7: ...t a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the damper into...

Страница 8: ...e energizing the outdoor unit See unit data label for proper incoming field wiring Any other wiring methods must be acceptable to authority having jurisdiction Providepowersupplyfortheunitinaccordance...

Страница 9: ...1650 T5 High 1950 Denotes Factory Set Low Speed Cooling Heating Denotes Factory Set High Speed Cooling Heating Denotes Factory Set Electric Heating Speed Overcurrent Protection Overcurrent protection...

Страница 10: ...a proper location Start Up Procedure The control circuit consists of an anti short cycle timer that will not let the compressor re start before 5 minutes have elapsed 1 Set the system mode to OFF and...

Страница 11: ...above the Terminate Temperature setting Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode reversing valve de energized Compressor will start immedia...

Страница 12: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspecttheelectricalconnectionsfortightness at the beginning of each heating and cooling season Service as necessary CAUTION Th...

Страница 13: ...Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 FIGURES TABLES Q5RD Length L Width W Height H A B 024K 49 35 22 2 40 15 7 61 030K 49 35...

Страница 14: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 139 258 115 141 260 121 281 121 143 262 126 283 126 304 126 145 266 129 285 131 306...

Страница 15: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 134 269 129 136 271 135 293 134 138 274 140 295 139 316 138 140 279 139 297 144 318...

Страница 16: ...s Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 130 277 124 298 121 318 119 132 279 129 300...

Страница 17: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Страница 18: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Страница 19: ...137 73 305 142 87 334 154 103 365 173 119 396 192 35 231 126 48 257 131 61 283 135 74 309 140 88 341 151 104 372 168 120 403 186 36 238 124 49 263 129 62 288 133 75 313 138 89 348 148 105 379 164 121...

Страница 20: ...D HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED R...

Страница 21: ...CK BLUE BLACK GREY BLACK ORANGE WHITE RED GREEN YELLOW RED BLUE ORANGE YELLOW GREY BROWN RED BROWN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 5 On models w n...

Страница 22: ...Accessory Heat Plug Outdoor Thermostat Factory Option Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat INDOOR T STAT SUB BASE Green DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Ac...

Страница 23: ...23...

Страница 24: ...ndusingcommonsenseplays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failuretofollowsafe...

Отзывы: