background image

7

Figure 6. Supply Damper

AUTOMATIC DAMPER IS CLOSED

WHEN HEAT PUMP IS OFF

MULTIPLE DUCT APPLICATION

SINGLE DUCT APPLICATION

Figure 5. Typical Duct Applications

Locating & Installing the Supply Damper(s)

When locating the supply damper(s), carefully 
check fl oor joists and frame members that could 
interfere with the installation of the damper or 
fl exible duct. Ideally, the damper (Figure 6) should 
be located in the bottom of the main duct, forward 
of center of the home, at least three feet from 
the nearest register. The round supply opening 
in the slanted side of the damper should face the 
side of the home where the heat pump is located.

1.  Locate the center of the heat duct by cutting 

a small hole in the fi berboard below the duct 
at the desired location.

2.  Cut a hole approximately 3/4” larger than the 

damper opening in the fi berboard.

3. Cut a 9-1/8” x 13-1/8” hole in the duct and 

bend over all tabs fl at on the inside of the 
heat duct. 

4.  Insert the damper into the duct and bend over 

all tabs fl at on the inside of the heat duct.

5.  Seal the opening between the fi berboard and 

damper or fl exible duct.

Elbow

Figure 7. Drain Trap

P-Trap

Condensate Drainage

A 3/4” condensate fi tting extends out of the side 
of the unit as shown in Figure 7. The drain trap, 
shipped in the electrical compartment, must be 
installed to prevent water from collecting inside 
the unit.
1.  Thread the elbow provided with the unit into 

the drain connection until hand tight.

2.   Connect the condensate tubing onto the fi tting, 

forming a trap near the drain connection. See 
Figure 7.

3.  Route the condensate tube from the trap to 

a suitable drain. 

NOTE:

 For proper drainage, 

make sure the trap is level to the ground and 
tubing outlet is below trap level.

Содержание Q5RD Series

Страница 1: ...check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified i...

Страница 2: ...Low Pressure Switch 13 High Pressure Switch 13 Unit Maintenance 13 Figures Tables 13 Figure 9 Unit Dimensions 13 Table 4 Q5RD Physical Data 13 Charging Tables Cooling Mode 14 Table 5 Q5RD X24K 2 Ton U...

Страница 3: ...f the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit will develop a coating of snow and ice on the heat transfer coil Thi...

Страница 4: ...tdoor coil must be maintained in order to achieve rated performance See Figure 2 page 5 for minimum clearances to obstructions Consideration should also be given to availability of electric power serv...

Страница 5: ...ngto NationalFireProtectionAssociation Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of Ame...

Страница 6: ...tion from under the home by cuttingasmallholeinthesub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located...

Страница 7: ...t a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the damper into...

Страница 8: ...e energizing the outdoor unit See unit data label for proper incoming field wiring Any other wiring methods must be acceptable to authority having jurisdiction Providepowersupplyfortheunitinaccordance...

Страница 9: ...1650 T5 High 1950 Denotes Factory Set Low Speed Cooling Heating Denotes Factory Set High Speed Cooling Heating Denotes Factory Set Electric Heating Speed Overcurrent Protection Overcurrent protection...

Страница 10: ...a proper location Start Up Procedure The control circuit consists of an anti short cycle timer that will not let the compressor re start before 5 minutes have elapsed 1 Set the system mode to OFF and...

Страница 11: ...above the Terminate Temperature setting Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode reversing valve de energized Compressor will start immedia...

Страница 12: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspecttheelectricalconnectionsfortightness at the beginning of each heating and cooling season Service as necessary CAUTION Th...

Страница 13: ...Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 FIGURES TABLES Q5RD Length L Width W Height H A B 024K 49 35 22 2 40 15 7 61 030K 49 35...

Страница 14: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 139 258 115 141 260 121 281 121 143 262 126 283 126 304 126 145 266 129 285 131 306...

Страница 15: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 134 269 129 136 271 135 293 134 138 274 140 295 139 316 138 140 279 139 297 144 318...

Страница 16: ...s Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 130 277 124 298 121 318 119 132 279 129 300...

Страница 17: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Страница 18: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Страница 19: ...137 73 305 142 87 334 154 103 365 173 119 396 192 35 231 126 48 257 131 61 283 135 74 309 140 88 341 151 104 372 168 120 403 186 36 238 124 49 263 129 62 288 133 75 313 138 89 348 148 105 379 164 121...

Страница 20: ...D HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED R...

Страница 21: ...CK BLUE BLACK GREY BLACK ORANGE WHITE RED GREEN YELLOW RED BLUE ORANGE YELLOW GREY BROWN RED BROWN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 5 On models w n...

Страница 22: ...Accessory Heat Plug Outdoor Thermostat Factory Option Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat INDOOR T STAT SUB BASE Green DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Ac...

Страница 23: ...23...

Страница 24: ...ndusingcommonsenseplays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failuretofollowsafe...

Отзывы: