background image

6

COMBUSTION AIR & VENTING REQUIREMENTS

 WARNING:

 AVERTISSEMENT:

CARBON MONOxIDE POISONING HAZARD

Failure  to  follow  the  steps  outlined  below  for 

each appliance connected to the venting system 

being placed into operation could result in carbon 

monoxide poisoning or death.
The following steps shall be followed with each 

individual  appliance  connected  to  the  venting 

system being placed in operation, while all other 

appliances connected to the venting system are 

not in operation:
1.  Seal  any  unused  openings  in  the  venting 

system.

2.  Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 or the CSA 

B149.1, Natural Gas and Propane Installation 

Codes and these instructions. Determine that 

there is no blockage or restriction, leakage, 

corrosion and other deficiencies which could 

cause an unsafe condition.

3.  As  far  as  practical,  close  all  building  doors 

and windows and all doors between the space 

in  which  the  appliance(s)  connected  to  the 

venting system are located and other spaces 

of the building.

4.  Close fireplace dampers.

5.  Turn on clothes dryers and any appliance not 

connected  to  the  venting  system.  Turn  on 

any exhaust fans, such as range hoods and 

bathroom exhausts, so they are operating at 

maximum  speed.  Do  not  operate  a  summer 

exhaust fan.

6.  Follow  the  lighting  instructions.  Place  the 

appliance  being  inspected  into  operation. 

Adjust the thermostat so appliance is operating 

continuously.

7.  Test  for  spillage  from  draft  hood  equipped 

appliances  at  the  draft  hood  relief  opening 

after 5 minutes of main burner operation. Use 

the flame of a match or candle.

8.  If improper venting is observed during any of 

the above tests, the venting system must be 

corrected in accordance with the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 and/or CSA 

B149.1, Natural Gas and Propane Installation 

Codes.

9.  After it has been determined that each appliance 

connected to the venting system properly vents 

when tested as outlined above, return doors, 

windows, exhaust fans, fireplace dampers and 

any other gas-fired burning appliance to their 

previous conditions of use.

RISQUE D’EMPOISONNEMENT AU MONOXYDE 

DE CARBONED

Le non-respect des consignes suivantes portant 

sur chacun des appareils raccordés au système 

d’évacuation  mis  en  service  pourrait  entraîner 

l’empoisennement au monoxyde de carbone ou 

la  mort.  Les  consignes  suivantes  doivent  être 

observées  pour  chaque  appareil  raccordé  au 

système d’évacuation mis en service si les autres 

appareils raccordés au système ne sont pas en 

service:

1.  Sceller toute ouverture non utilisée de la systéme 

d’évacuation;

2.  S’assurer que la systéme d’évacuation présente 

des  dimensions  et  une  pente  horizontale 

conformes  à  la  norme  ANSI  Z223.1/NFPA 

54,  intitulée  National  Fuel  Gas  Code  ou  aux 

codes  d’installation  CSA-B149.1,  ainsi  qu’aux 

présentes instructions. S’assurer que la systéme 

d’évacuation  n’est  pas  bloquée,  restreinte, 

corrodée, qu’elle ne fuit pas et qu’elle ne présente 

aucun autre défaut potentiellement dangereux;

3.  Dans la mesure du possible, fermer toutes les 

portes et fenêtres du bâtiment, et toutes les portes 

entre la pièce où se trouve l’appareil raccordé à 

la systéme d’évacuation et les autres pièces du 

bâtiment.

4.  Fermer les registres des foyers;

5.  Mettre  en  service  les  sécheuses  et  tout  autre 

appareil  qui  n’est  pas  raccordé  à  la  systéme 

d’évacuation. Faire fonctionner à régime maximal 

tout ventilateur d’évacuation, tel que les hottes de 

cuisinière et les ventilateurs de salles de bains. 

Ne pas mettre en service les ventilateurs d’été.

6.  Respecter les instructions d’allumage. Mettre en 

service l’appareil à l’essai. Régler le thermostat 

de manière à ce que l’appareil fonctionne sans 

interruption;

7.  Vérifier  s’il  y  a  débordement  à  l’orifice 

d’évacuation du coupe tirage des appareils dotés 

d’un  coupe  tirage  5  minutes  après  l’allumage 

du  brûleur  principal.  Utiliser  la  flamme  d’une 

allumette ou d’une chandelle.

8.  Si  l’on  constate,  au  cours  de  l’un  des  essais 

qui précèdent, que l’évacuation est déficiente, 

corriger le système d’évacuation conformément 

à la norm ANSI Z223.1/NFPA 54, National Fuel 

Gas Code, et (ou) aux codes d’installation CSA 

B149.1.

9.  Après  avoir  déterminé  que  tous  les  appareils 

raccordés à la systéme d’évacuation évacuent 

correctement  tel  que  prescrit  ci-dessus, 

rouvrir les portes et les fenêtres et remettre les 

ventilateurs d’évacuation, les registres de foyers 

et tout autre appareil fonctionnant au gaz à leur 

état de fonctionnement initial.

Содержание iHybrid DF6SF-X24K080CA

Страница 1: ...urrait entra ner des blessures graves la mort ou des dommages mat riels L installation et l entretien doivent tre effectu s par un installateur qualifi un organisme de service ou le fournisseur de gaz...

Страница 2: ...System Cooling 16 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 17 Verifying Over Temperature Limit Control Operation 17 Verifying Burner Operation 17 Mani...

Страница 3: ...is material may cause respiratory irritations or may cause lung cancer Fiberglass wool may also cause eye irritation skin sensitization or other allergic responses in susceptible individuals Always we...

Страница 4: ...osition as shown on page 5 Use only with the type of gas approved for this unit Refer to the unit rating plate Provide adequate combustion and ventilation air to the unit See page 6 and page 7 Provide...

Страница 5: ...vey the job site to determine the best location for the packagedunit Theunitshouldbelocatedwithconsideration of minimizing the length of the supply and return ducts Consideration should also be given...

Страница 6: ...f use RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONEd Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l empoi...

Страница 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Страница 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Страница 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Страница 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Страница 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Страница 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Страница 13: ...d damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLterminalo...

Страница 14: ...be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided...

Страница 15: ...y bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases If pressure testing the gas supply lines at pr...

Страница 16: ...ondensatedrainage Verify all clearance requirements are met and there is free airflow to and from the outdoor coil Verify that the duct work is sealed to prevent air leakage Verifythatthelinevoltagepo...

Страница 17: ...ases the temperature rise and a higher speed decreases the temperature rise The unit is equipped with a variable speed motor Heating and cooling speed selection is made by changing the tap settings on...

Страница 18: ...essure switch If the pressure switch is closed the heat mode sequence will not continue If it remains closed for 10 seconds the red LED will flash 3 times repetitively until the fault condition clears...

Страница 19: ...rculating blower will then ramp to approximately 3 4 of the selected airflow for another 30 seconds before adjusting to full airflow until the thermostat is satisfied 4 If the thermostat is not satisf...

Страница 20: ...er temperature limit switch and pressure switch 6 Remove the silicone rubber tube from the collector pan to the pressure switch 7 Remove4nutssecuringthecombustionblowertothecollector pan Remove the co...

Страница 21: ...through the heat exchanger tubes and venting the gases through the vent system for both high and low fire conditions GasValve Thegasvalvecontrolstheflowofgastotheburners in both low and high fire Whe...

Страница 22: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights Mode...

Страница 23: ...10 4 T O N 1440 Normal 800 Normal 3 T O N 970 1600 5 T O N 1600 10 880 10 1065 10 1760 TAP B 10 810 TAP B 10 1050 TAP B 10 1530 Normal 900 Normal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 T...

Страница 24: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Страница 25: ...tir la compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais ut...

Страница 26: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Страница 27: ...BL UE WHIT E WHIT E WIRING DIA GRAM 208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIA GRAM NOTES 1 Disconne ct power be f ore ser v icing 2 F or sup...

Страница 28: ...R S THERMOST AT L ON LY WHITE WHITE 208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIA GRAM NOTES 1 Disconnec t power be f ore ser v icing 2 F or supp...

Страница 29: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Страница 30: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting Miswired Module Indication Recommended Troubles...

Страница 31: ...nd repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices wh...

Страница 32: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Страница 33: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ..._________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical conne...

Отзывы: