background image

8

CIRCULATING AIR SUPPLY

 WARNING:

Products  of  combustion  must  not  be  allowed  to 

enter the return air ductwork or the circulating air 

supply. Failure to prevent products of combustion 

from being circulated into the living space can create 

potentially hazardous conditions including carbon 

monoxide poisoning that could result in personal 

injury or death.
All return ductwork must be adequately sealed, all 

joints  must  be  taped,  and  the  ductwork  must  be 

secured to the unit with sheet metal screws. When 

return air is provided through the bottom of the unit, 

the joint between the unit and the return air plenum 

must be air tight.
The roof curb or cement pad on which the unit is 

mounted must provide sound physical support of 

the unit with no gaps, cracks, or sagging between 

the unit and the curb or pad.
Return  air  and  circulating  air  ductwork  must  not 

be connected to any other heat producing device 

such as a fireplace insert, stove, etc. Doing so may 

result in fire, explosion, carbon monoxide poisoning, 

personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return duct. 

Air ducts should be installed in accordance with the standards 

of the National Fire Protection Association “Standard for 

Installation of Air Conditioning Systems” (NFPA 90A), “Standard 

for Installation of Residence Type Warm Air Heating and Air 

Conditioning Systems” (NFPA 90B), and all applicable local 

codes. NFPA publications are available by writing to: National 

Fire Protection Association, Batterymarch Park, Quincy, ME 

02269 or visit www.NFPA.org on the web.

• 

Design the duct work according to Manual D by the Air 
Conditioning Contractors of America (ACCA).

• 

The ducts must be properly sized not to exceed the unit 
maximum ESP rating at 400 scfm per nominal ton of cooling 
capacity.

• 

Duct work should be attached directly to the unit flanges for 
horizontal applications.

•  If 

roof curb is installed, the ducts must be attached to the 

curb hangers, not the unit.

•  It is recommended that the outlet duct be provided with a 

removable access panel. The opening should be accessible 

when the unit is installed in service and shall be sizes so that 

smoke or reflected light may be observed inside the casing 

to indicate the presence of leaks in the heat exchanger. The 

cover for the opening shall be attached in a way that will 

prevent leaks.

•  If outside air is utilized as return air to the unit for ventilation 

or to improve indoor air quality, the system must be designed 

so that the return air to the unit is not less than 50° F (10° 

C) during heating operation.

•  If a combination of indoor and outdoor air is used, the ducts 

and damper system must be designed so that the return air 

supply to the furnace is equal to the return air supply under 

normal, indoor return air applications.

Air Filter Requirements

 WARNING:

Never  operate  the  unit  without  a  filter  in  place. 

Dust  and  lint  could  accumulate  on  internal  parts, 

resulting in loss of efficiency, equipment damage 

and possible fire.

•  This unit is not supplied with air filter(s) and has no factory 

equipped means for accommodating internal filter(s). A 

suitable air filter must be installed upstream of the evaporator 
coil of the return air system. Refer to 

Table 1

 

for recommended 

filter sizes.

•  All return air must pass through the filters before entering 

the evaporator coil.

 

It is important that all filters be kept clean 

and replaced frequently to ensure proper operation of unit. 

Dirty or clogged filters will reduce the efficiency of the unit 

and result in unit shutdowns.

•  Air filter pressure drop must not exceed 0.08 inches WC.

•  Horizontal and downflow Installations require the air filter 

system be installed in the return air ductwork.

NOTE TO INSTALLER:

 After installing or replacing the 

filtration system for this unit, add the following statement 

on or adjacent to the filter service panel: 

“Replace filter(s) 

installed in your system only with the same dimensional 

size filters that are being replaced.”

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. Refer 

to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical lining 

inside the supply duct work.

• 

Acoustical insulation must be in accordance with the current 
revision of the Sheet Metal and Air Conditioning Contractors 
National Association (SMACNA) application standard for 
duct liners.

• 

Duct lining must be UL classified batts or blankets with a 
fire hazard classification of FHC-25/50 or less.

• 

Fiber duct work may be used in place of internal duct liners if 
the fiber duct work is in accordance with the current revision 
of the SMACNA construction standard on fibrous glass ducts. 

Table 1. Air Filter Requirements

NOMINAL
COOLING

(TONNAGE)

APPROXIMATE

AIR FLOW

RANGE (CFM)

APPROXIMATE

FILTER AREA

(SQ. IN.)*

RECOMMENDED

FILTER SIZE

(IN. x IN.)

2

700 - 900

450

20 x 25

3

1,000 - 1,300

625

25 x 25

4

1,500 - 1,900

915

18 x 25 (2 required)

5

1,600 - 2,000

975

20 x 25 (2 required)

* Based on velocity of 300 ft/min for disposable filters.

Содержание iHybrid DF6SF-X24K080CA

Страница 1: ...urrait entra ner des blessures graves la mort ou des dommages mat riels L installation et l entretien doivent tre effectu s par un installateur qualifi un organisme de service ou le fournisseur de gaz...

Страница 2: ...System Cooling 16 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 17 Verifying Over Temperature Limit Control Operation 17 Verifying Burner Operation 17 Mani...

Страница 3: ...is material may cause respiratory irritations or may cause lung cancer Fiberglass wool may also cause eye irritation skin sensitization or other allergic responses in susceptible individuals Always we...

Страница 4: ...osition as shown on page 5 Use only with the type of gas approved for this unit Refer to the unit rating plate Provide adequate combustion and ventilation air to the unit See page 6 and page 7 Provide...

Страница 5: ...vey the job site to determine the best location for the packagedunit Theunitshouldbelocatedwithconsideration of minimizing the length of the supply and return ducts Consideration should also be given...

Страница 6: ...f use RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONEd Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l empoi...

Страница 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Страница 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Страница 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Страница 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Страница 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Страница 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Страница 13: ...d damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLterminalo...

Страница 14: ...be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided...

Страница 15: ...y bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases If pressure testing the gas supply lines at pr...

Страница 16: ...ondensatedrainage Verify all clearance requirements are met and there is free airflow to and from the outdoor coil Verify that the duct work is sealed to prevent air leakage Verifythatthelinevoltagepo...

Страница 17: ...ases the temperature rise and a higher speed decreases the temperature rise The unit is equipped with a variable speed motor Heating and cooling speed selection is made by changing the tap settings on...

Страница 18: ...essure switch If the pressure switch is closed the heat mode sequence will not continue If it remains closed for 10 seconds the red LED will flash 3 times repetitively until the fault condition clears...

Страница 19: ...rculating blower will then ramp to approximately 3 4 of the selected airflow for another 30 seconds before adjusting to full airflow until the thermostat is satisfied 4 If the thermostat is not satisf...

Страница 20: ...er temperature limit switch and pressure switch 6 Remove the silicone rubber tube from the collector pan to the pressure switch 7 Remove4nutssecuringthecombustionblowertothecollector pan Remove the co...

Страница 21: ...through the heat exchanger tubes and venting the gases through the vent system for both high and low fire conditions GasValve Thegasvalvecontrolstheflowofgastotheburners in both low and high fire Whe...

Страница 22: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights Mode...

Страница 23: ...10 4 T O N 1440 Normal 800 Normal 3 T O N 970 1600 5 T O N 1600 10 880 10 1065 10 1760 TAP B 10 810 TAP B 10 1050 TAP B 10 1530 Normal 900 Normal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 T...

Страница 24: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Страница 25: ...tir la compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais ut...

Страница 26: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Страница 27: ...BL UE WHIT E WHIT E WIRING DIA GRAM 208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIA GRAM NOTES 1 Disconne ct power be f ore ser v icing 2 F or sup...

Страница 28: ...R S THERMOST AT L ON LY WHITE WHITE 208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIA GRAM NOTES 1 Disconnec t power be f ore ser v icing 2 F or supp...

Страница 29: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Страница 30: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting Miswired Module Indication Recommended Troubles...

Страница 31: ...nd repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices wh...

Страница 32: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Страница 33: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ..._________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical conne...

Отзывы: