Common steam and condensate line errors
1. Steam hose not led at least 300 mm perpendicularly upwards before
first bend.
2. Minimum bend radius of steam hose of 300 mm not maintained (forming
of condensate).
3. Siphon of the condensate hose not at least 300 mm below the steam
distribution pipe.
4. No condensate drain installed at vertical transition.
5 . Steam hose not sloped (slope min. 20 %).