– Steam distribution pipe is mounted
less than 500 mm above the top
edge of the humidifier
:
Initially, the steam hose is led with an
upslope of at least 20 % over a
minimum height of 300 mm
above the top edge of the humidifier and
then down to the steam distribution pipe with a
minimum slope of 5 %
.
The condensate hose is led down with a
minimum slope of 20 %
, in
the form of a
siphon (min. hose bend diameter Ø200 mm)
, directly
into a discharge funnel.
Important!
Before putting the unit into operation, the siphon of the
condensate hose must be filled with water.
Obstacle
Install condensate drain (accessory)
at the lowest point