36
Example
given:
ϕ
1= 30 %rh,
ϕ
2= 70 %rh
humidification distance B
N
:
1,4 m
(
0.36 m
for steam distribution system
MultiPipe
)
Note: If the humidification distance has to be reduced for technical reasons,
the amount of steam per unit must be divided between
several steam
distribution pipes
or the
steam distribution system MultiPipe
must be
used. If this is the case, contact your Nordmann supplier.
Minimum distances to be observed
To prevent the water vapour, that is emitting from the steam distribution pipe,
from condensing on downstream system components, a minimum distance
to the steam distribution pipe must be observed (depends on the humidifi
cation distance “B
N
”).
0.5 x B
N
50 mm
after expansion
0.5 x B
N
1 x B
N
before bend
1 x B
N
before/after constriction
before branch
Содержание AT4 13064
Страница 1: ...MOUNTING INSTRUCTIONS Steam humidifier Nordmann AT4 2559419 EN 1310 NORDMANN E N G I N E E R I N G...
Страница 2: ......
Страница 64: ...64 Notes...
Страница 65: ...65 Notes...
Страница 66: ...Notes...
Страница 67: ...Nordmann Engineering Ltd Printed in Switzerland Technical modifications reserved...