3.3 Motors for use in Zone 21 and Zone 22 according to EN 60079 and
IEC 60079
Pos: 108 /Anleitungen/Motor en/B1091 Dr ehstromm otoren/Sicherheitshinw eise/GEF AHR_ATEX - Explosi onsgefahr El ektischer Schl ag - Motor en [B1091] @ 11\m od_1460010132024_388.docx @ 316266 @ @ 1
DANGER!
Explosion hazard
All work must only be carried out with the machine at a standstill and the
power to the system
switched off
.
Higher temperatures than the maximum permitted surface temperature of the housing may
be present inside the motor. The motor must therefore never be opened in an explosive
atmosphere!
Failure to comply with this may result in the ignition of an explosive atmosphere.
Pos: 109 /Anleitungen/Motor en/B1091 Dr ehstromm otoren/Sicherheitshinw eise/WARNUN G_AT EX_Expl osionsg efahr-Thermisch - M otor en [B1091] @ 11\m od_1460010112266_388.docx @ 316231 @ @ 1
WARNING
Explosion hazard
Excessively heavy dust deposits must be avoided, as these impair the cooling of the device!
Impairment or obstruction of the flow of cooling air, for example due to partial or large area
coverage of the fan cover or the entry of foreign bodies fall into the fan must be avoided in
order to ensure adequate cooling.
Only cable glands and reducers which are approved for use in explosion hazard areas may
be used.
All cable glands which are not used must be closed with blind screw plugs which are approved
for potentially explosive areas.
Only the original seals may be used.
Failure to comply increases the risk of ignition of an explosive atmosphere.
Pos: 110 /Anleitungen/Motor en/B1091 Dr ehstromm otoren/3. ATEX/!2! Motor en für den Einsatz in der Z one 21 und Z one 22 nach EN 60079- 0 sowie IEC 60079_02 [Zon21+ 22] @ 83\m od_1638957466222_388.docx @ 2849978 @ @ 1
For these motors, the following information specifically or complimentarily apply.
Motors which comply with EN 60079 and IEC 60079 are suitable according to their labelling for use in
zone 21 or zone 22 - non-conductive dust.
Type suffix:
According to
EN 60079
Zone 21
2D
e.g.:
80 L/4 2D TF
Zone 22
3D
e.g.:
80 L/4 3D TF
According to
IEC 60079
Zone 21
EPL Db
e.g.:
80 L/4 IDB TF
Zone 22
EPL Dc
e.g.:
80 L/4 IDC TF
Labelling:
According to
IEC 60079 and
2014/34 EU
0102
II 2D Ex tb IIIC T125°C Db
For category 2 (zone 21)
1)
II 3D Ex tc IIIB T125°C Dc
For category 3 (zone 22 –
non-conducting dust)
1)
According to
IEC 60079
EX tb IIIC T125°C Db
For category 2
1)
Ex tc IIIB T125°C Dc
For category 3 (zone 22 –
non-conducting dust)
1)
1)
The indicated surface temperature may deviate from 125 °C and can be found on the name plate.
Содержание 6051302
Страница 1: ...B 1091 en Motors Operating and Assembly Instructions...
Страница 6: ...Motors Operating and Assembly Instructions 6 B 1091 en 2722...
Страница 66: ...Motors Operating and Assembly Instructions 66 B 1091 en 2722 5 Declarations of Conformity...
Страница 67: ...Table of Contents B 1091 en 2722 67...
Страница 68: ...Motors Operating and Assembly Instructions 68 B 1091 en 2722...
Страница 71: ...Table of Contents B 1091 en 2722 71 Ende der Liste f r Textm arke Inhalt...
Страница 72: ...6051302 2722...