START-S5PV
Technical manual
-15-
5.3 Working time memorization with PARTIAL OPENING control
The PARTIAL OPENING control can be used for a partial opening of the door and permit the passage of people or small
vehicles just to avoid the complete opening of the gate.
ON
CTS
2
1
4
3
6
5
8
7
10
9
1
Put the dip-switch no.5 of DIPA in ON
The gate is closed
2
Press the PARTIAL OPENING button (everything
which is connected to the input no.20 or 2nd chan-
nel of the remote control)
L’automazione parte
in APERTURA
3
Press the PARTIAL OPENING to stop the gate in
the special point (stop partial opening)
L’automazione si ARRESTA
4
Let the gates open
L’automazione è
in “TEMPO DI PAUSA”
5
Press PARTIAL OPENING to start closing
L’automazione parte
in CHIUSURA
6
Wait that the gate stopping automatically
L’automazione è in posizio-
ne di CHIUSO
7
Put in OFF the micro-switch no.5 of DIPA to back
to the normal status. The signal light is turning off
and the green l.e.d. goes back to the normal status.
End of the operation
5.4 Increase the PAUSE TIME
It is possible to increase the pause time without learning the
working time. When the gate is on pause, by each pression of
P button, the pause time increase of 4 seconds. There are fi ve
pression to increase the pause time up to 20 sec (5 pressions
x 4 seconds). After six pressions, the pause time goes back at
2 seconds (l.e.d. START and PARTIAL OPENING are fl ashing).
+ 4s
+ 4s
+ 4s
+ 4s
Time changing by
each pression
Beginning time
This operation is possible
when the gate is on pause
while opening.
PARTIAL
OPENING