Introduction     

5.

Product Guide     

 VISI-SWITCH

®

INSTALLATION

The switch can be mounted on timber poles with a 
keyhole arrangement or concrete poles using banded 

straps. The following types of installations are supported:

•   Mounted to the pole above the powerline

•  Mounted to the pole below the powerline

Prior to mounting on the pole, the switch must be fitted 
to the mounting bracket and all surge arrestors and 
cable tails fitted.  

The hanging bracket can be mounted above or below 
the cross arm depending on the customer’s preferred 
installation location. 

The switch is completely symmetrical so it can be 
mounted with the hook stick operator facing toward the 
pole or away from the pole.  

The switch assembly can be fixed to the pole via a 
crane, pole mounted hoist or EPV. Lifting points are 
provided to allow for lifting of the assembled switch.  

The switch is to remain within 15 degrees of horizontal 

whilst lifting.  An M12 stud on the switch is provided for 

an earth connection. A minimum thickness of 35mm

2

 

copper conductor must be used.  

Standard hand tools will be all that is required to 
complete the installation, namely ring, adjustable 

VISI-SWITCH

®

 POLE MOUNTING ARRANGEMENT

(ABOVE THE POWER LINE WITH FEET) 

VISI-SWITCH

®

 POLE MOUNTING ARRANGEMENT

(BELOW THE POWER LINE)

TUNNEL 

CONNECTOR

TWO HOLE NEMA

PAD OPTION

spanners or allen key.  All fasteners must be 
capable of withstanding the maximum load 
applied by a man with a standard spanner.

VISI-SWITCH

®  

POLE 

MOUNTING ARRANGEMENT

Содержание VISI-SWITCH OLB15-16-800

Страница 1: ... VISI SWITCH VISI SWITCH OLB15 16 800 12KV MODEL PRODUCT GUIDE ...

Страница 2: ...15 16 800 has a rated maximum voltage of 12 kV a rated continuous current of 800 A and a short time current withstand of 16 kA for 3 seconds Each phase is comprised of a vacuum interrupter with solid dielectric insulation and a built in isolator to provide physical isolation in accordance with the requirements of insulation coordination standards IEC 60071 1 Insulation co ordination Part 1 Definit...

Страница 3: ... to isolate sections of feeders for maintenance work In recent years older air break switches which could not be operated while the feeder was under load have been replaced by gas switches While enclosed gas switches address the reliability deficiencies of air break switches it comes at a cost of compromised safety because maintenance staff can no longer visually check that all three phases are is...

Страница 4: ...d with a single motion using either an extended hook stick which reaches directly to the switch or a shorter hook stick which connects to an insulated down rod extending from the switch The advantage of the switch is that the operator can view the isolator contacts through the viewing window thereby readily determining the state of the switch from the ground In particular the operator can confirm ...

Страница 5: ...g window allows a clear view of the state of the switch from an operator standing on the ground The isolator contact is coated with an iridescent reflective paint in the colour red and can be easily seen through the window even at night with the use of a torch The window is designed to remain transparent during the entire life of the switch without any discolouration It is scratch resistant and ca...

Страница 6: ...r facing toward the pole or away from the pole The switch assembly can be fixed to the pole via a crane pole mounted hoist or EPV Lifting points are provided to allow for lifting of the assembled switch The switch is to remain within 15 degrees of horizontal whilst lifting An M12 stud on the switch is provided for an earth connection A minimum thickness of 35mm2 copper conductor must be used Stand...

Страница 7: ...PEN STATE 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 VISI SWITCH SIDE VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS VISI SWITCH FRONT VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS An insulated down rod extending from the switch can be used to move the operating mechanism further down the ...

Страница 8: ... Current Rated Distribution Line Closed Loop Breaking Current Short time current withstand Fault Make Capacity RMS Fault Make Capacity Peak Mainly Active Load Breaking Rated Cable Charging Breaking Current Rated Line Charging Breaking Current Rated Cable and Line Charging Breaking Current under Earth Fault Conditions Rated Earth Fault Breaking Current Mechanical Operations Full Load Operations Fau...