Introduction     

NOJA Power’s VISI-SWITCH

®

 is a solid dielectric load 

break switch designed for manual isolation in a three-
phase electricity distribution grid feeder. Unique to 
this switch, is the viewing window embedded in the 
bushings, allowing an operator to see the actual point 
of isolation.  Through the viewing window, an operator 
can see the isolator electrical contacts when the switch 
is closed and visible isolation when the switch is open, 
guaranteeing that the circuit is isolated. 

It also features vacuum interrupters with solid dielectric 
insulation and a unique and patent-pending drive 
mechanism ensuring safe operational sequence.

NOJA Power’s VISI-SWITCH

®

 OLB15-16-800 has a 

rated maximum voltage of 12 kV, a rated continuous 
current of 800 A and a short time current withstand of 
16 kA (for 3 seconds).  

Each phase is comprised of a vacuum interrupter with 
solid dielectric insulation and a built-in isolator to provide 
physical isolation in accordance with the requirements 
of insulation coordination standards IEC 60071-1 

Insulation  co-ordination  –  Part  1:  Definition,  Principles 
and Rules and IEC 60071-2 Insulation co-ordination – 
Part 2: Application Guide.

The VISI-SWITCH

®

 features a unique and patent-

pending  drive mechanism which connects the vacuum 
interrupters to the isolators and guarantees both parts 
of the switch will open once operation is initiated. The 
sequencing of the complete switching operation is 

VISI-SWITCH

®

 WITH SURGE 

ARRESTORS

VISI-SWITCH

®

 SIDE VIEW

VISI-SWITCH

®

 FRONT VIEW

INTRODUCTION

1.

Product Guide     

 VISI-SWITCH

®

Содержание VISI-SWITCH OLB15-16-800

Страница 1: ... VISI SWITCH VISI SWITCH OLB15 16 800 12KV MODEL PRODUCT GUIDE ...

Страница 2: ...15 16 800 has a rated maximum voltage of 12 kV a rated continuous current of 800 A and a short time current withstand of 16 kA for 3 seconds Each phase is comprised of a vacuum interrupter with solid dielectric insulation and a built in isolator to provide physical isolation in accordance with the requirements of insulation coordination standards IEC 60071 1 Insulation co ordination Part 1 Definit...

Страница 3: ... to isolate sections of feeders for maintenance work In recent years older air break switches which could not be operated while the feeder was under load have been replaced by gas switches While enclosed gas switches address the reliability deficiencies of air break switches it comes at a cost of compromised safety because maintenance staff can no longer visually check that all three phases are is...

Страница 4: ...d with a single motion using either an extended hook stick which reaches directly to the switch or a shorter hook stick which connects to an insulated down rod extending from the switch The advantage of the switch is that the operator can view the isolator contacts through the viewing window thereby readily determining the state of the switch from the ground In particular the operator can confirm ...

Страница 5: ...g window allows a clear view of the state of the switch from an operator standing on the ground The isolator contact is coated with an iridescent reflective paint in the colour red and can be easily seen through the window even at night with the use of a torch The window is designed to remain transparent during the entire life of the switch without any discolouration It is scratch resistant and ca...

Страница 6: ...r facing toward the pole or away from the pole The switch assembly can be fixed to the pole via a crane pole mounted hoist or EPV Lifting points are provided to allow for lifting of the assembled switch The switch is to remain within 15 degrees of horizontal whilst lifting An M12 stud on the switch is provided for an earth connection A minimum thickness of 35mm2 copper conductor must be used Stand...

Страница 7: ...PEN STATE 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 VISI SWITCH SIDE VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS VISI SWITCH FRONT VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS An insulated down rod extending from the switch can be used to move the operating mechanism further down the ...

Страница 8: ... Current Rated Distribution Line Closed Loop Breaking Current Short time current withstand Fault Make Capacity RMS Fault Make Capacity Peak Mainly Active Load Breaking Rated Cable Charging Breaking Current Rated Line Charging Breaking Current Rated Cable and Line Charging Breaking Current under Earth Fault Conditions Rated Earth Fault Breaking Current Mechanical Operations Full Load Operations Fau...

Отзывы: