Introduction     

3.

Product Guide     

 VISI-SWITCH

®

NOJA Power’s VISI-SWITCH

®

 is an enclosed three 

phase load break switch with visible isolation.  It is used 
to isolate sections of feeders for maintenance work so 
that work can be carried out in a safe manner.

The VISI-SWITCH

®

 includes an isolator and 

vacuum interrupter for each phase that are serially 
interconnected for load break application.  A mechanical 
driving mechanism is provided for driving open and 
closed each pair of electrical contacts and is configured 
to control the sequence of the opening and closing of 
the contacts. The vacuum interrupter is opened first 
to break current flow and then after a short delay the 
isolators are opened to disconnect the electrical circuit. 
When closing, the isolator closes first and then the 
vacuum interrupter, making the current.

The operator can manually open and close the contacts 
of both the isolator and interrupter from the ground 
with a single motion using either an extended hook 
stick which reaches directly to the switch or a shorter 
hook stick which connects to an insulated down rod 
extending from the switch. 

The advantage of the switch is that the operator can 
view the isolator contacts through the viewing window, 
thereby readily determining the state of the switch from 
the ground. In particular, the operator can confirm that 
there is a visible break i.e. the contacts are open and 
that the associated circuit is safely isolated.

The switch includes isolator bushings in which the 
electrical isolator contacts are located, a metal tank in 
which the driving mechanism is located, and interrupter 
bushings in which the interrupter contacts are located. 
The bushings and the tank are sealed together and 
impede the ingress of moisture thereby suiting the 
assembly to outdoor use. The tank is manufactured 
from powder coated stainless steel and is arc-fault 
vented.  It has a 30 year operating life and the entire 
device is rated to IP65.

OVERVIEW

VISI-SWITCH

®

 FRONT VIEW

VISI-SWITCH

®

  VISIBLE ISOLATOR 

OPEN STATE

VISI-SWITCH

®

  VISIBLE ISOLATOR 

CLOSED STATE

Содержание VISI-SWITCH OLB15-16-800

Страница 1: ... VISI SWITCH VISI SWITCH OLB15 16 800 12KV MODEL PRODUCT GUIDE ...

Страница 2: ...15 16 800 has a rated maximum voltage of 12 kV a rated continuous current of 800 A and a short time current withstand of 16 kA for 3 seconds Each phase is comprised of a vacuum interrupter with solid dielectric insulation and a built in isolator to provide physical isolation in accordance with the requirements of insulation coordination standards IEC 60071 1 Insulation co ordination Part 1 Definit...

Страница 3: ... to isolate sections of feeders for maintenance work In recent years older air break switches which could not be operated while the feeder was under load have been replaced by gas switches While enclosed gas switches address the reliability deficiencies of air break switches it comes at a cost of compromised safety because maintenance staff can no longer visually check that all three phases are is...

Страница 4: ...d with a single motion using either an extended hook stick which reaches directly to the switch or a shorter hook stick which connects to an insulated down rod extending from the switch The advantage of the switch is that the operator can view the isolator contacts through the viewing window thereby readily determining the state of the switch from the ground In particular the operator can confirm ...

Страница 5: ...g window allows a clear view of the state of the switch from an operator standing on the ground The isolator contact is coated with an iridescent reflective paint in the colour red and can be easily seen through the window even at night with the use of a torch The window is designed to remain transparent during the entire life of the switch without any discolouration It is scratch resistant and ca...

Страница 6: ...r facing toward the pole or away from the pole The switch assembly can be fixed to the pole via a crane pole mounted hoist or EPV Lifting points are provided to allow for lifting of the assembled switch The switch is to remain within 15 degrees of horizontal whilst lifting An M12 stud on the switch is provided for an earth connection A minimum thickness of 35mm2 copper conductor must be used Stand...

Страница 7: ...PEN STATE 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 VISI SWITCH SIDE VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS VISI SWITCH FRONT VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS An insulated down rod extending from the switch can be used to move the operating mechanism further down the ...

Страница 8: ... Current Rated Distribution Line Closed Loop Breaking Current Short time current withstand Fault Make Capacity RMS Fault Make Capacity Peak Mainly Active Load Breaking Rated Cable Charging Breaking Current Rated Line Charging Breaking Current Rated Cable and Line Charging Breaking Current under Earth Fault Conditions Rated Earth Fault Breaking Current Mechanical Operations Full Load Operations Fau...

Отзывы: