background image

Introduction     

VISIBLE ISOLATOR OPEN POSITION

VISIBLE ISOLATOR PULLS BACK INTO 

OPEN POSITION

VISIBLE ISOLATOR CLOSED POSITION

1.

2.

Product Guide 

     VISI-SWITCH

®

dictated by the drive mechanism which rapidly opens the 
vacuum interrupters to break the current and then, after 
a short delay, opens the isolators. The viewing window 
embedded in the isolator bushings can be seen from 
the ground allowing maintenance staff to confirm that 
the switch has been isolated prior to commencing work.

The product has been extensively type tested by 
independent laboratories to ensure long life and reliability 
under the harshest environmental conditions. The VISI-
SWITCH

®

 can operate in extreme temperatures, over 

a -40 to 55

o

C temperature range, 0 to 100 percent 

humidity, and meets specified ratings up to a height of 
1000 m (functional up to 3000 m with derating). The unit 
is designed to cope with exposure to salt spray, dust, 
smoke and corrosive gases, vapours and liquids. The 
viewing window is scratch resistant and can withstand 
impact such as hail according to IK08. 

Utilities employ three-phase load break switches to 
isolate sections of feeders for maintenance work. In 
recent years, older air break switches, which could not 
be operated while the feeder was under load have been 
replaced by gas switches. While enclosed gas switches 
address the reliability deficiencies of air break switches, 
it comes at a cost of compromised safety because 
maintenance staff can no longer visually check that 
all three phases are isolated before starting work on 
the feeder. SF6 has also been identified as the most 
potent greenhouse gas and utilities will most likely incur 
the cost of disposing the SF6 gas at the end of life of 
the switch. 

NOJA Power’s engineers have designed the 
VISI-SWITCH

®

 to overcome the drawbacks of gas 

load break switches providing the linesmen with visible 
break confirmation that the switchgear has isolated the 
line before commencing work. Furthermore, the units 
are far more environmentally friendly than existing 
solutions because the solid dielectric eliminates the use 
of a potent greenhouse gas. Like all other switchgear 
products designed and manufactured by NOJA Power it 
also features controlled arc fault venting.  

The VISI-SWITCH

®

 demonstrates NOJA Power’s 

ongoing commitment to the environment, quality and 
safety making the VISI-SWITCH

®

 OLB15-16-800 the 

ideal choice for today’s smart grids.

Содержание VISI-SWITCH OLB15-16-800

Страница 1: ... VISI SWITCH VISI SWITCH OLB15 16 800 12KV MODEL PRODUCT GUIDE ...

Страница 2: ...15 16 800 has a rated maximum voltage of 12 kV a rated continuous current of 800 A and a short time current withstand of 16 kA for 3 seconds Each phase is comprised of a vacuum interrupter with solid dielectric insulation and a built in isolator to provide physical isolation in accordance with the requirements of insulation coordination standards IEC 60071 1 Insulation co ordination Part 1 Definit...

Страница 3: ... to isolate sections of feeders for maintenance work In recent years older air break switches which could not be operated while the feeder was under load have been replaced by gas switches While enclosed gas switches address the reliability deficiencies of air break switches it comes at a cost of compromised safety because maintenance staff can no longer visually check that all three phases are is...

Страница 4: ...d with a single motion using either an extended hook stick which reaches directly to the switch or a shorter hook stick which connects to an insulated down rod extending from the switch The advantage of the switch is that the operator can view the isolator contacts through the viewing window thereby readily determining the state of the switch from the ground In particular the operator can confirm ...

Страница 5: ...g window allows a clear view of the state of the switch from an operator standing on the ground The isolator contact is coated with an iridescent reflective paint in the colour red and can be easily seen through the window even at night with the use of a torch The window is designed to remain transparent during the entire life of the switch without any discolouration It is scratch resistant and ca...

Страница 6: ...r facing toward the pole or away from the pole The switch assembly can be fixed to the pole via a crane pole mounted hoist or EPV Lifting points are provided to allow for lifting of the assembled switch The switch is to remain within 15 degrees of horizontal whilst lifting An M12 stud on the switch is provided for an earth connection A minimum thickness of 35mm2 copper conductor must be used Stand...

Страница 7: ...PEN STATE 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 VISI SWITCH SIDE VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS VISI SWITCH FRONT VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS An insulated down rod extending from the switch can be used to move the operating mechanism further down the ...

Страница 8: ... Current Rated Distribution Line Closed Loop Breaking Current Short time current withstand Fault Make Capacity RMS Fault Make Capacity Peak Mainly Active Load Breaking Rated Cable Charging Breaking Current Rated Line Charging Breaking Current Rated Cable and Line Charging Breaking Current under Earth Fault Conditions Rated Earth Fault Breaking Current Mechanical Operations Full Load Operations Fau...