User Manual 07
User Manual 06
Product parameters
Type
A32Q
A32R
A32H
ASD32Q
ASD32R
ASD32H
Pole
3P/4P
3P/4P
Installation
Fixed/Withdrawable
Fixed/Withdrawable
Rated current(A)
800/1600/2000/2500/3200
Fixed
:
800/1600/2000/2500
Withdrawable
:
800/1600/2000/2500/3200
Rated Maximum Valatge(V)
254/508/635
254/508/635
Frequency(Hz)
50/60
50/60
Interrupting rating at rated maximum voltage (kA)
254V
65
85
100
/
/
/
508V
65
85
100
/
/
/
635V
65
85
100
/
/
/
Short time withstand current (kA)
254V
65
85
100
65
85
100
508V
65
85
100
65
85
100
635V
65
85
100
65
85
100
operating time(ms)
open
<
70
<
70
close
<
40
<
40
life cycle(time)
mechanical
without maintenance
10000
10000
10000
10000
10000
10000
with maintenance
/
/
/
/
/
/
electrical
without maintenance
6000
6000
6000
6000
6000
6000
with maintenance
/
/
/
/
/
/
Enclosure dimension
H
×
W
×
D(in/mm)
withdrawable
3P
21.65
×
23.62
×
18.11
(550
×
520
×
460)
Ventilation Area Top: 9092mm²
Bottom
:
9092mm²
21.65
×
23.62
×
18.11
(550
×
520
×
460)
Ventilation Area Top: 9092mm²
Bottom: 9092mm²
4P
21.65
×
25
×
18.11
(550
×
635
×
460)
Ventilation Area Top: 11963mm²
Bottom: 11963mm²
21.65
×
25
×
18.11
(550
×
635
×
460)
Ventilation Area Top: 11963mm²
Bottom: 11963mm²
fixed
3P
21.65
×
20.47
×
14.17
(550
×
520
×
360)
21.65
×
20.47
×
14.17
(550
×
520
×
360)
4P
21.65
×
25
×
14.17
(550
×
635
×
360)
21.65
×
25
×
14.17
(550
×
635
×
360)
Mounting type
Rated current/A
Power Consumption/W
Withdrawable
800
80
Withdrawable
1600
300
Withdrawable
2000
400
Withdrawable
2500
500
Withdrawable
3200
620
Fixed
800
50
Fixed
1600
200
Fixed
2000
250
Fixed
2500
300
Fixed
3200
430
A32 Bus bar recommendation
In
Vertical
Horizontal
Qty
Size(in)
Size(mm)
Qty
Size(in)
Size(mm)
800A
1
1/4
×
3
6.35
×
76.2
1
1/4
×
3
6.35
×
76.2
1600A
2
1/4
×
3
6.35
×
76.2
2
1/4
×
3
6.35
×
76.2
2000A
2
1/4
×
4
6.35
×
101.6
3
1/4
×
3
6.35
×
76.2
2500A
3
1/4
×
4
6.35
×
101.6
5
1/4
×
3
6.35
×
76.2
3200A
4
1/4
×
4
6.35
×
101.6
Recommended tighting torque is 40-50 N.m.
Note: These tables should be used as a general guideline only, the solution used should take into consideration the varieties of switchgear types and conditions.
Environmental Conditions
Ambient temperature
Altitude
Humidity
Rated
Current(A)
Temperature(
℃
)
<40
45
50
55
60
65
70
800
100%
100%
100%
100%
100%
100%
100%
1
6
00
100%
100%
100%
100%
100%
100%
100%
2000
100%
100%
100%
100%
100%
100%
93%
2500
100%
95%
92%
88%
83%
80%
75%
3200
100%
95%
92%
88%
83%
80%
75%
Altitude(m)
<2000
2600
3900
4900
Rated Voltage(V)
1xUe
0.95xUe
0.8xUe
0.7xUe
Rated Current(A)
1xIn
0.99xIn
0.96xIn
0.94xIn
A32 Circuit breakers can operate in the following environmental conditions:
With M Smart Unit: -40
℃
~ 70
℃
;
With H Smart Unit: -20
℃
~ 70
℃
;
A32 Circuit breakers can operate at higher temperatures than the reference temperature 40
℃
,in this case,the derating coefficients
shown in the table must be applied.
A32 Circuit breakers do not undergo changes in rated performance up to 2000m.Beyond this altitude ,the derating coefficients shown in
the table must be applied.
The relative humidity does not exceed 85% at 40
℃
,the monthly average maximum of relative humidity in the wettest month does not
exceed 90%.
The effect of surface condensation caused by temperature changes on product performance should be taken into consideration.