Auto reboot: If enabled, UPS will auto recover when AC is recovering. Vice
versa.
•
Bypass when UPS is off: If enabled, AC will directly provide power to con
-
nected devices when UPS is off. Vice versa.
•
Converter mode: If enabled, the UPS will operate in converter mode. Vice
versa.
•
ECO mode: If enabled, the UPS will operate in ECO mode when input
voltage is within acceptable range. Vice versa.
•
Battery open status check: If enabled, the monitored UPS will check if the
battery connection is ok or not when UPS is turned on.
•
Cold start: If disabled, the UPS can be turned on only when AC is normally
connected to UPS. Vice versa.
•
Bypass not allowed: If enabled, the UPS will not transfer to bypass mode
under any conditions. If disabled, the UPS will be allowed to transfer to
bypass mode according to UPS internal setting.
•
Battery deep-discharge protection: If enabled, the monitored UPS shuts
down in accordance with the condition of battery and load on battery
mode to protect battery. Vice versa.
•
Site fault detection: If enabled, the monitored UPS will beep when the
input neutral and hot wires are reversed. Vice versa.
•
P1 Programmable outlet control (battery mode): If enabled, when UPS is
running at battery mode, it will cut off P1 outlets after backup setting time
arrives. If disabled, UPS will provide continuous power to P1 outlets until
the battery is running out.
•
Outlet setting: Users can set limited backup time for P1 outlets when UPS
is on battery mode.
•
Battery numbers setting: Set battery numbers in parallel.
•
Voltage and frequency range for bypass mode: Set acceptable voltage and
frequency range in bypass mode
•
Maximum and minimum voltage: When UPS is on bypass mode and
input voltage is out of setting range, UPS will enter battery mode.
•
Maximum and minimum frequency: When UPS is on bypass mode and
input frequency is out of setting range, UPS will enter battery mode.
•
Voltage range for ECO mode: Set acceptable voltage range for ECO mode.
4.3 Control
4.3.1 Real-time control
Select
Control >> Real-time control
. Refer to Chart 4-5.
Chart 4-5
You can real-time control the UPS by executing following operation:
•
UPS turn On/Off: Click “On” to turn on the UPS and “Off” to turn off the
UPS immediately.
•
Battery Self-Test: It offers three types of battery self-test: 10-second self-
test, deep discharge test, and self-defined self-test. Simply clicking “Start”
button from each type. It will execute the self-test immediately.
4.4 System configuration
4.4.1 Web user
It configures the authority to access SNMP web pro. Please enter access
ID and password in each column. There is no limitation to access control in
default setting. It is also allowed for http and https modification. The default
setting is 80 for http and 443 for https. If any modification for adding web
users, deleting web users or port re-configuration, it’s necessary to click “Re
-
start Web Server” button to restart web server to activate all modifications.
Refer to Chart 4-6.