Shutdown the PC while battery mode: When selected, integrated with
Shutdown Wizard, local PC will shut down while UPS works on battery
mode.
•
Time needed for shutting down the PC: Enter the delay time to shut down
the operating system.
•
The PC should:
1. Shutdown: When clicking the checkbox, the selected system will shut
down. The default setting is clicked.
2. Sleep mode: When clicking the checkbox, selected system will suspend
the system instead of a normal shutdown. But this function is only
supported by Windows 2000 or higher on supported hardware.
•
Also power off the UPS after shutting down the PC: When click the check
-
box, monitored UPS will turn off after local system shuts down. The UPS
shutdown time will be later than system complete shutdown time. Users
can choose to shut down the system without shutting down the UPS.
•
Shutdown UPS output after xx sec: It will cut off UPS output after moni
-
tored UPS works on battery mode for xx sec.
•
Shutdown the PC while low battery: When clicking this checkbox, local
PC will shut down when monitored UPS battery is running low.
•
Wake on LAN while AC recovery: When clicking this checkbox, the local
PC will be wake on LAN while AC recovery.
•
Send E-mail while any UPS event occurs: When clicking this checkbox, it
will send alarm E-mail when any event occurs on the local UPS.
•
Send SMS while any UPS event occurs: When clicking this checkbox, in
the event of an alarm condition occurring, a message about UPS status
will be sent to the specified users via mobile phone.
•
EMD alarming temperature upper limit: Set up alarm for high temperature
point. If detected temperature is beyond setting value, it will send alarm
message.
•
EMD alarming humidity upper limit: Set up alarm for high humidity point.
If detected humidity is beyond setting value, it will send alarm message.
•
Data record interval xx sec: Data log record the data per xx sec.
4.4.7 Scheduled
Select
System Configuration >> Scheduled
. Refer to Chart 4-12.
Chart 4-12
•
Scheduled battery selft est: Scheduled battery selft est can be executed
once, daily, weekly, or monthly. Users can select UPS and time parame
-
ters. It is recommended to set only one action in the same time. If mul
-
tiple actions have been applied at the same time, some of these actions
may be ignored. Any action will be ignored when the action is not sup
-
ported by the UPS.
•
Scheduled UPS on/off: Scheduled UPS on/off can be executed once, daily,
weekly. Users can select UPS and time parameters. It is recommended to
set only one action in the same time. If multiple actions have been applied
at the same time, some of these actions may be ignored. Any action will
be ignored when the action is not supported by the UPS.