Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014
Page 79
9.6.4 CAL Menu „Digital outputs“
Selecting the >Digital outputs< menu requires to enter the PIN (2718) once
again. This ensures to prevent unauthorised persons from performing simula-
tions during operation.
Choose the desired relays to be simulated by using the >up< and >down< arrow
keys. Use ENTER to either turn the chosen relay ON or OFF directly. The relays
will de-energise if you exit the menu
.
Fig. 9-80
Relay simulation
9.6.5 CAL Menu „Simulation“
After entering the PIN code >2718< select between level, velocity and medium
temperature by using the >up< and >down< arrow keys. Pressing >right< or
>left< will increase or decrease the simulated flow velocity or temperature value
in steps of 1 cm or 0.1 °C.
Using ENTER enables to enter the desired simulation value directly.
The flow value which has been calculated by means of the simulated readings
will be indicated on the bottom line of the screen. Relays which might have been
set will switch and programmed mA outputs supply according current values
simultaneously. Use >up< or >down< keys to indicate output values in the bot-
tom line of the display.
1
Simulated height/level
2
Simulated flow velocity
3
Simulated medium temperature
4
Calculated simulated flow value
5
Programmed relay activated by simulation
6
Analog output signals
Fig. 9-81
Simulation mode