TuV�
(13)
SC HE DU LE
(14)
EC-Type-Examination Certificate No. TOV 14 ATEX 142076
(15) Description of equipment
The Ex-Separator-Module type iXT0-xxx is used for supply of sensors and for communication of
sensors with measuring transmitters.
The following executions of the Ex-Separator-Module type iXT0-xxx are available:
- iXT0-420: Ex-Separator-Module for connection to 4 x RS485 and 2 x 2 wire sensors
- iXT0-421: Ex-Separator-Module for connection to 4 x RS485 and 2 x 2 wire sensors with 1 x HART
function
- iXT0-21 0: Ex-Separator-Module for connection to 2 x RS485 and 1 x 2 wire sensors
- iXT0-211: Ex-Separator-Module for connection to 2 x RS485 and 1 x 2 wire sensors with 1 x HART
function
The permissible ambient temperature range is -20 °C ... +40 °C.
Electrical data
Supply circuit ............................................ U
n
= 12 V d. c. (11 ... 13 V d. c.)
(Terminals X2, 4 [+], X2, 3 [GND];
U
m
= 253 Va. c.
X2, 5 [shield connection], X2, 6 [PE))
Pea. 9 W
RS485 circuit
..
.
.
.
...
.
.
.
...
.
.
..
..
..
..
.
.
.......
.
..
.
..
.
..
.
. U
n
= 5 V d. c.
(Terminals
U
m
= 253 Va. c.
X2, 1 [RxTx+], X2, 2 [RxTx-])
2 wire analogous sensor circuit .................. in type of protection Intrinsic Safety Ex ib 11B
(Terminals X4, 6/7 (optional with HART]; Maximum values per circuit:
X6, 6/7)
U
0
= 25.4 V
10
=
89.2 mA
P
o
= 567 mW
characteristic line: linear
max. permissible external
10 mH
1 mH
0.5 mH
inductance
max. permissible external
370 nF
420 nF
510 nF
capacitance
0.1 mH
810 nF
page 2/3