BKI15ATEX0013X/1
pdf4012m0600p_06
21 / 24
P11: dcba Setting range,* damping, noise suppression, error indication on the output current *
FACTORY DEFAULT: 0000
a
Range
can be selected with the 3-wire models for 4 – 20 mA or 0 – 20 mA. Setting is important in respect to the output current error
indication.
b
Damping
can be used to reduce unwanted fluctuation of the displayed value
c Noise
suppression
is for eliminating possible disturbance coming from the mains
d Error indication on the current output
of the 3-wire models is used to indicate error signals arriving as input current and the error of the
UNICONT
itself according the chart below. Simultaneous occurrence of both errors is going to result output current to be the error indication
of the
UNICONT
.
*
For 3-wire models only
Attention
: character „
a
” is at the right end (this is the first to blink)
a
Range selection
d
Error indication on the current output
0
4 – 20mA
UNICONT
error
Error indication on the input current*
1
0– 20mA
Current > 20 mA
Current < 4 mA
0
3.8 mA
3.8 mA
3.8 mA
b
Damping
1 22
mA
0
3 s
2
22 mA
3.8 mA
1
5 s
3
22 mA
2
10 s
4
22 mA
3.8 mA
3.8 mA
3
20 s
5
22 mA
6
22 mA
3.8 mA
c
Noise suppression
7 22
mA
0
50 Hz
1
60 Hz
*– If an error indication of 22 mA arrives (from a transmitter) to the input of the
UNICONT
, with settings 5 (under
d)
than it means that the current
output of the
UNICONT
is 3.8 mA (and with setting 6 it is 22 mA)
– If an error indication of 3.8 mA arrives (from a transmitter) to the input of the
UNICONT
, with settings 1 (under
d)
than it means that the current
output of the
UNICONT
is 22 mA (and with setting 6 it is 3.8 mA mA)