20 / 24
pdf4012m0600p_06
BKI15ATEX0013X/1
0
Da
-9999
Db
29999
D
0
3,
85m
A
Ia
21
m
A
Iin (mA)
Displayed
value
Input
current
Figure 9. Display curve of 2-wire models
0
Da
-9999
Db
29999
D
0
3,
85m
A
3,
9m
A
Ia
20,
5m
A
21m
A
Iin (mA)
Displayed
value
Input
current
Figure10. Display curve of 3-wire models
with input range set for 4 – 20 mA
0
Da
-9999
Db
29999
D
0
20,
5m
A
21m
A
Iin (mA)
Ia
Displayed
value
Input
current
Figure 11. Display curve of 3-wire models
with input range set for 0 – 20 mA
P9: - - - a Current generator test
(for 3-wire models only)
In this parameter the actual current output is displayed. Going to the parameter value the output current of 3.6 – 22 mA can be set by the keys
and
. The c
urrent value entered this way should conform with the output current measured with an ammeter.
P10: - - - a Setting the decimal point
FACTORY DEFAULT: 0002
Important remark:
modification of P10 represents resetting parameter values to the FACTORY DEFAULT. Thus, it is suggested that
programming starts with knowing the range of values to be displayed and programming P10 first.
a
Position of decimal point
0
xx.xxx
1
xxx.xx
2
xxxx.x
3
xxxxx