P01: - - b a Measurement Mode
This mode determines the primary value transmitted by the current output or the HART
®
protocol communication, and the displayed value.
It also determines the value, which will be assigned to the relay operation.
a
M
EASUREMENT
M
ODE
T
RANSMITTED
VALUE
D
ISPLAY
SYMBOL
D
ISPLAYED
V
ALUES
Attention! Mind
the sequence!
At this
parameter, the
value "a" on the
right will blink
first.
0
Distance Distance
DIST
Distance
1
Level
Level
LEV
Level,
Distance
2
Level in percentage
LEV%
Level in percentage *, Level, Distance
3
Volume
Volume
VOL
Volume, Level, Distance
4
Volume in percentage
VOL%
Volume in percentage *, Volume, Level, Distance
b
B
ARGRAPH INDICATION
* The displayed value depends on the current output parameters (
P10, P11
)
0
Echo strength
1
Current output
FACTORY DEFAULT:
P01
= 11
P02: - c b a Calculation units
a
T
EMPERATURE
Attention!
Mind the sequence!
At this parameter, the value "a" on the right will blink first.
0
°C
1
°F
This table is interpreted by
P00(c)
,
P01(a)
and
P02(c)
and is irrelevant in the case of percentage measurement (
P01(a)= 2
or
4
).
b
V
OLUME
M
ASS
(see details:
P32
)
Metric
US
Metric
US
0
m
3
ft
3
tonne (1000 kg)
lb (pound)
1
liter
gallon
tonne (1000 kg) Ton (2000 pounds)
c
T
IME
0
s
1
min
2
hour
3
day FACTORY DEFAULT:
P02
=
000