P19: - - - -
HART
®
Polling Address
The polling address can be set here between 0 and 15. For a single instrument, the polling address is 0, the output changes in the 3.8…22 mA
range (analog output), and HART
®
is also working. If multiple units (up to 15) are used in HART
®
Multidrop mode, the polling addresses must be
other than 0 (1…15), the output current will be a constant 4 mA, and information is only transmitted via HART
®
. For other aspects of setting this
parameter, see the EView software manual that came with your HART
®
device.
FACTORY DEFAULT:
P19
= 00
5.4.4.
Measurement Optimization
P20: - - - a Damping time
The damping time is used to dampen (filter out) unwanted fluctuations in the display and output. Increasing the value reduces the fluctuation,
while the end value of a rapid change is delayed on the display and output by the damping time.
a
D
AMPING TIME
[s]
G
RANULES
particle size > 2…3
mm
(> 0.08…0.12
″
)
P
OWDERS
particle size < 1…2
mm
(< 0.04…0.08
″
)
0
no filtering
Recommended for testing only
1
3
not applicable
not applicable
2
6
not applicable
not applicable
3
10
not applicable
not applicable
4
30 applicable not
applicable
5
60 recommended applicable
6
100 recommended recommended
7
300 recommended recommended
8
600 recommended recommended
9
1000 applicable applicable
FACTORY DEFAULT:
P20
= 300 s