6.4.4.
Digital output
6.4.4.1
HART polling address
Parameter: P19
Menu path:
OUTPUT SETUP / SERIAL OUTPUT / ADDRESS
Default value:
0
Description:
HART polling address (only HART capable types)
The polling address can be set between 0 and 15. For a single instrument the polling
address is 0 and the output is 4...20mA (analogue output). If multiple units are used in
HART Multidrop mode (max. 15pcs) the polling addresses should differ from 0 (1-15), in
this case the output current will be fixed at 4mA. The fixed 4mA output can be overwritten
as described in chapter
6.4.2.5
.
6.4.5.
Service functions
6.4.5.1
Security codes
User security code
Parameter: -
Menu path:
SERVICE / SECURITY / USER LOCK
Default value:
0
Description:
Setting or unlocking the user security code.
The instrument can be protected against unauthorized programming with a 4 digit PIN
(Personal Identification Number) code. If either of the digits differs from 0 the code is
active. If zero is specified, then the secret code has been deleted!
In case of Active code, this code is requested at menu entry.
Service code
Parameter: -
Menu path:
SERVICE / SECURITY / SERVICE LOCK
Description:
Setting of the service code (only for trained personnel)!