38 / 60
le00100a0600p_05
BKI 11 ATEX 0012 X
A. Calculated value of the output current. After the dimension, the mode of current output is indicated by inverse
inscription:
Manual mode (see
6.4.2.1
)
H
HART address is not 0, so output current has become overwritten to 4mA (see
6.4.2.1
)
Analogue transmission reacts to a programmed failure condition if an upper or lower fault current is programmed.
(see
6.4.2.4
)
B. Output range (4…20mA) indicated in a bargraph.
C. Relay state indication: if deenergized – C1 closed, C2 open, there is no indication. If RELAY message is visible, the relay is energised – C2 closed, C1 open.
D. Indication of Menu Lock:
If key symbol is visible, the unit is protected with a password. When entering the menu, the instrument asks for the correct password.
If REM message is visible, the instrument is in remote programming mode and the menu cannot be accessed.
Errors occurred during the measurement can be seen at the bottom line of the display.