INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

TROUBLE SHOOTING

Problem 

Cause 

Solution 

Actuator 
does not 
move. 

Faulty wiring.   

Correct the wiring. 

 

Voltage and 
input signal are 
not coming. 

Check the voltage and 
input signal.   

 

Incorrect 
voltage. 

When it's burned out by 
excess voltage, replace 
the actuator.   

 

Connection or 
wiring is not 
correct.   

Correct the miswiring 
and misconnection.   
Be careful not to 
mistake the plus and 
minus of wiring. 

 

Short the circuit, 
contact failure. 

Review wires and 
connection. 

 

Motor is too old.  Replace the actuator. 

Operation 
is unstable. 

Excess surge or 
voltage was 
applied. 

Replace the actuator. 

 

Rainwater 
entered the 
actuator. 

 

Added high 
harmonics noise 
from an inverter. 

Attachment a filter for 
each inverter maker 
option.   

 

Effect of high 
level noise. 

Use the shielded wire 
and ground the wiring.   
Separate signal wire 
from power line.   

Problem 

Cause 

Solution 

Stop in the 
mid position. 

• Biting of 

valve seat.   

• The scale 

has adhered 
to the valve 
trim. 

Remove a foreign 
object.   

 

 

Clean or replace valve 
parts.   
(NH)   

 

Overload 
protector runs 
because of 
over-torque.   

Motor protection circuit 
returns by the signal of 
operation of an 
opposite direction. Turn 
on the power again. 

Leakage 
from   
valve body 

• Valve cap 

get loose.   

• Valve body is 

damaged. 

Replace the valve. 
(NS  NP) 

Leakage 
from   
valve seat   

Seat is worn   
or damaged. 

Replace the valve. 
Replace the actuator. 

 

Loose 
seal-spring, 
damage. 

Replace seal-spring.   

Leakage 
from   
valve trim 

Packing is 
worn or 
distorted. 

Replace the valve. 

 

 

Tighten the gland nut.   
(NH)   

For more information contact   
NIPPON VALVE CONTROLS, INC. for consultation. 

Содержание Vpro NS

Страница 1: ...pe Linear L A X N S 0 5 U U F 0 EQ L A X N S 0 5 U U F X E 1 5 NH type L A X N H 0 5 U U T 0 NP type L A X N P 0 1 K K T 0 1 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1 Actuator LAX 2 Valve NS NH NP 3 Voltage 1...

Страница 2: ...MPa 1 MPa Size mm 10 to 15 10 to 15 15 Material Body SCS14A SUS316 PEEK Trim SUS316 SUS316 HCr PLTD PEEK Seat F PTFE SUS316 None Stem seal Packing F PTFE PTFE PTFE Allowable Leak Rate Bubble tight Cl...

Страница 3: ...oint it at the time of the order Indication signal 0 mA SHUT 1 mA OPEN External load resistance less than 3 k Common in mode A B Resolution Less than 0 2 Duty cycle 100 200 V AC 100 110 220 V AC 50 30...

Страница 4: ...t us if you need to adjust trimmer Terminal board Mode A LAX 070 Adjustment of dead band Adjustment of dead band is useful to prevent hunting of the actuator Turning D B trimmer clockwise increases th...

Страница 5: ...ent distortion of the valve ENVIRONMENT Do not install in place where corrosive gas is present or where vibration is heavy 0 5 G or more When radiant heat causes the surface temperature of the control...

Страница 6: ...ver put anything on the actuator or make it into a foothold ADJUSTABLE RANGE OF STROKE LAX 030 SHUT by an input signal 4 mA and shipped It is not necessary to adjust the stroke LAX 070 SHUT by an inpu...

Страница 7: ...Replace the actuator Rainwater entered the actuator Added high harmonics noise from an inverter Attachment a filter for each inverter maker option Effect of high level noise Use the shielded wire and...

Отзывы: